- panel RTE Zone parameter must be set to the next consecutive zone
number (for example, 2).
- keypad parameter Zone must be set to the same value as Door Zone (for
example, 1)
- keypad parameter RTE as Next Zone must be enabled
•
Timers: This submenu contains all the timers associated with a door. Access
this menu to adjust times if the application needs times other than the default
time.
- Door Unlock Time: The number of seconds the door remains unlocked when
a user presents credentials to access the door. The user can open the door
during this time.
- Door Zone Shunt Time: The time the door can remain open before the zone
creates an alarm.
- Door Zone Warning Time: The time remaining in the shunt timer when a
door warning condition becomes active. Keypad sounders and relay outputs
can then be programmed to sound a sounder to notify the user of a pending
shunt expiration.
•
Door Options: Use the option to select the desired behaviour of the door.
- Door Forced Reporting: When the selected Door type supports the Forced
Door feature, ticking this box causes the Forced Door Alarm to be reported off
premises.
- Door Left Open Reporting: When the Door Type selected supports the DLO
feature, ticking this box causes the DLO Alarm to be reported off premises.
- Log Door Access: Ticking this box will cause a logging event when the door
is unlocked. This event identifies the Door and the user that opened it.
- Mag Lock: Enable the option to prevent the lock from engaging until the door
is closed for the Pre-Lock time. If enabled, the door will remain unlocked until
it is closed.
Note:
Door relay may be wired either to a dedicated Door Lock output on
NXG-1832 / NXG-1833-EUR keypad, or to any output in the system (on the
panel or on an output expander).
•
The door relay wired to the NXG-1832 / NXG-1833-EUR keypad
Set the Door parameter in keypad's programming settings, to the desired
door number. The dedicated keypad output would follow the Unlock state of
the selected door.
•
Door relay wired to a system output
Configure an Action as follows:
- Function: Follow
- Event1: Category: Doors
- Event1: Type: Door Unlocked
- Event1: Start/End Range: door numbers.
64
xGenConnect Installation and Programming Guide