INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Product description: Control system strategy
Mounting the unit,
Step
continued
10
7
Mount the front
cover again
8
Make a water trap which meets the measurements on the picture and pour water in
it. Alternatively you can use the water trap from Dantherm (accessories):
9
Connect the hose to the drain – The drain pipe must be kept frost proof all the way,
to ensure that the water can run unhindered.
The drain pipe must at least fall by 1 % all the way from the unit to the drain outlet.
Dantherm A/S recommends insulated flex ducts when connecting to connectors/
coupling connectors. The ducts must be completely stretched to avoid un-neces-
sary loss of pressure.
Make sure you connect the ducts to the right connectors: The ducts must not
"hang" from the unit without support.
Dantherm recommends that the ducts are mounted with a flexible hose con-nec-
tion, to make the connection easier and to attenuate noise and vibrations from the
installation.