Mounting the unit,
continued
28
Step
5
Mount the drainage hose*) on the connection piece. The hose can be difficult to
connect to the connection piece. When the hose is about to be mounted it can be
helpful to warm up the hose prior to mounting, thereby it will be more flexible to
work with. Use lubricant on the hose if necessary, so that it can smooth over the
connection piece and maybe a hose clamp (not delivered)
*) Drainage hose is not supplied. Use a 3/4" reinforced hose, which cannot be bro-
ken or crushed flat. Dantherm recommends a transparent type with iron wire, so it
is possible to inspect the water trap
6
Lead the drainage hose through the ceiling construction and insulate up above the
hose connection piece:
Make sure that the drainage and drain pipe are always complete frost proof. A
frozen drain pipe can lead to damage. If it cannot be assured to keep the drainage
and drain pipe frost proof, Dantherm recommends connecting a heating cable
around the drain pipe. See more about this in the accessories list in the sec-tion
"Accessories" in the user's guide.
Entire drain pipe
must be frost proof.
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS