INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Product description: Control system strategy
Mounting the unit,
Step
continued
3
Build a wood construction which is levelled in both directions according to the
illustrations. The construction must be constructed of plates that can sustain the
weight of the unit (HCH5 MKII = 52 kg and HCH 8 = 70 kg). Make sure that there is
minimum 50 mm compressed insulation between the two plates to prevent any
vibrations from the unit to be transferred to the building.
Make the construction so that the unit slopes backwards against the drain. Place a
20 mm rise below the front of the unit as shown:
4
Place the unit on the
construction and make sure it
is levelled as illus-trated
Action
1000 mm
1500 mm
100 mm