3.21 Event Log

The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are numbered
1-1000, with 1 being the most recent. Each event is displayed with the date and time of the event, the number of the event, a
code to indicate whether the event was a warning (W), shutdown (S), or informational notice (I), the engine hours at the time of
the event, and the event description.
The time and date for notices (I) are not stored in the controller.
Procedure to View Event History
1.
Press Select to enter the main menu.
2.
Press the down arrow to step down to the event log.
3.
Press Select to display the most recent event.
4.
Press the down arrow to step to the next event.
5.
Use the up and down arrow buttons to view events.
6.
Press the Select button to exit the event log.
To stop viewing the event history before the last event, press the select button to return to the main menu.
Press UP and Down arrow buttons to scroll through events
Press Select button at any time to return to the main menu.
Figure 53
Event Log
64
Event Log --->
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours
event name
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours