3.20 Load Control Menus

The Load Control menu displays the status of the load management device inputs and outputs, and allows a test of the load
control output relays. This menu appears only if a load management device (load shed kit or Model RXT transfer switch with th e
combined interface/ load management board) is connected.
Generator current is displayed as a percent of the maximum generator capacity. The load control module adds and sheds loads
based on the generator current.
The test function cycles the relays in the order of their priority. For detailed information, refer to the instructions provided with
the load shed kit. For the RXT combined interface/ load management board, refer to the RXT automatic transfer switch Operation
and Installation Manual.
Load - - >
Control
Figure 52
Load Control Status Menu
TP-7092
11/22
Generator
Current: 123 %
Load - - >
Control 1
<- - Return
Test Outputs
Push Select (blinking)
Input 1:
In/Active
Input 2:
In/Active
Output 1:
Add/Shed
Output 2:
Add/Shed
Output 3:
Add/Shed
Output 4:
Add/Shed
Output 5:
Add/Shed
Output 6:
Add/Shed
<- - Return