Fault Message
Figure 24
Clearing a Fault on the RDC2 Controller
Warning (W) or
Fault Message
Shutdown (SD)
W (1 sec.)
AC Sens Loss
SD (3 sec.) *
Accy PwrOver
Warning
Advanced
Diagnostic
ATS ComError
ATS PhaseRot
Aux Input
SD *
Batt Chg Flt
Battery CrLo
Warning
Battery Voltage
High
Battery Voltage
Low
Engine Speed
SD *
High
Engine Speed
SD *
Low
Exer Not Sch
TP-7092
11/22
Overview --->
1.2 h
Condition
AC sensing lost. In Auto mode, generator output AC sensing
is lost. Detection begins10 seconds after crank disconnect.
Warning: after 1 second if no output detected after crank
disconnect.
Shutdown: after 3 seconds if voltage was present and then
lost.
Accessory Power Overload. An over current fault (short
W
circuit) on the accessory controller power output.
Shutdown during the reduced speed portion of an exercise.
The event history will show Advanced Diagnostic Active. The
SD
engine then restarts, runs at full speed for 2 minutes, and
stops. The controller returns to AUTO mode. The exercise
schedule does not change.
ATS communication error. Warning is displayed if ATS
W
interface connection is lost. See the section title: ATS
Communication Errors.
ATS phase rotation mismatch. Transfer switch phase rotation
W
does not match, ATS will not transfer.
Auxiliary input. An optional customer-connected input is
closed. (Digital input from optional PIM.)
Battery charger fault. Input to PIM from an external battery
W
charger (not the built-in battery charger).
Engine starting battery voltage falls below 11 VDC for more
than 10 seconds. Inhibited during the engine crank cycle.
W
Clears when the battery voltage returns to an acceptable
level.
Engine starting battery voltage rises above 16 VDC for more
than 10 seconds. Inhibited during the engine crank cycle.
W
Clears when the battery voltage returns to an acceptable
level.
Engine starting battery voltage falls below 12.5 VDC for more
than 90 seconds when the engine is not running. Not
W
operative during the engine crank cycle.
Clears when the battery voltage returns to an acceptable
level.
Engine speed exceeds 115% of the normal running speed for
more than 0.3 seconds.
Engine speed drops below 85% of the normal running speed
for more than 3 seconds.
Exercise not scheduled. No exercise is scheduled on the
W
controller.
Fault Message
Press UP arrow button.
Confirm Clear
Fault: NO
Confirm Clear
Fault: YES
tp6809
Check
Contact an authorized dealer
for service.
Contact an authorized dealer
for service.
If the generator set does not
restart and return to AUTO,
check for other faults that
prevent generator set
operation.
Check communication wiring
between transfer switch
interface board and generator
set.
Correct the ATS connection.
Refer to the ATS Installation
manual, wiring diagrams, and
labels on the transfer switch.
Check customer-supplied
equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger
operation.
Charge or replace the battery.
Check the battery rating and
condition.
Check the battery charger
operation.
Check the battery rating and
condition.
Check the battery charger
operation.
Charge or replace the battery.
Contact an authorized dealer
for service.
Reduce the load.
Check enclosure thermostat
and reset if tripped. Contact an
authorized dealer for service.
See the Setting the Exerciser
section for instructions to set
the exerciser.
35