UPS2000-H-(6 kVA–10 kVA)
Quick Guide
Step 3 Start the UPS in normal mode using one of the following methods.
Table 2-4 Startup methods
Startup Method
Method 1: When the UPS works in
bypass mode, hold down the button on
the UPS panel for more than 5s.
Release the button when the inverter
indicator blinks and you hear a beep
sound. Do not press any button during
inverter startup. When the startup
command is successfully delivered, and
the inverter indicator is steady on, the
UPS enters normal mode.
Method 2: In bypass mode, choose
Config > Control > Power-on/off on
the app to start the UPS. After
successful startup, the UPS enters
normal mode.
Issue 01 (2022-06-30)
Item
Description
Batteries in a
Specifies the number of
battery
batteries in a battery string.
string
Set this parameter based
on the actual configuration.
This parameter is
configurable in non-
battery mode.
Single
Specifies the capacity of
battery
each battery in a battery
capacity
string connected in series.
(Ah)
This parameter is
configurable in non-
battery mode.
Number of
Specifies the number of
battery
battery strings connected in
strings
parallel. This parameter is
configurable in non-
battery mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On Commissioning
Setting
Set as
required.
Set as
required.
Set as
required.
Figure
Value Range
The value
range
depends on
the voltage of
a single
battery. The
default value
is 0.
7–1000. The
default value
is 0.
1–4. The
default value
is 0.
51