Materials; Power Cables - Huawei UPS2000-H Quick Manual

Hide thumbs Also See for UPS2000-H:
Table of Contents

Advertisement

UPS2000-H-(6 kVA–10 kVA)
Quick Guide
Other tools
Electrician's knife

1.1.3 Materials

Item
Standard
material
Auxiliary
material
Optional
material

1.1.4 Power Cables

● A circuit breaker needs to be installed in the upstream of the UPS to facilitate
● The UPS can generate large leakage currents. An RCD is not recommended. If
● The leakage current of the 6 kVA UPS and 10 kVA UPS is less than or equal to
Issue 01 (2022-06-30)
Tweezer
Description
This type of materials is
delivered with the equipment
and can be obtained from the
fittings bag.
Customers can purchase this
type of materials from the
supplier or other vendors.
Customers can purchase this
type of materials from the
supplier based on application
scenarios.
NO TICE
maintenance.
leakage protection is required, select a recommended circuit breaker.
50 mA, respectively. When selecting an RCD, consider the leakage current of
the UPS and its downstream loads.
Copyright © Huawei Digital Power Technologies Co., Ltd.
1 Installation and Cable Connection
Brush
Type
Materials in the packing list
Power cable
Battery
Vacuum cleaner
5