GE AF-650 GP PROFINET Operating Instructions Manual page 62

Table of Contents

Advertisement

Warnings and Alarms
No.
Description
82
CSIV parameter error
85
Profibus/Profisafe Error
90
Encoder Loss
91
Analog input 54 wrong settings
243
Brake IGBT
244
Heatsink temp
245
Heatsink sensor
246
Pwr.card supply
247
Pwr.card temp
248
Illegal PS config
250
New spare part
251
New Model Number
Table 11.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Can not be Auto reset via H-04 Auto-Reset (Times)
A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset button or
make a reset by a digital input (Parameter group E-1# [1]). The origin event that caused an alarm cannot damage the frequency
converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to frequency
converter or connected parts. A Trip Lock situation can only be reset by a power cycling.
LED indication
Warning
Alarm
Trip locked
PROFINET Operating Instruction
Warning
Alarm/Trip
(X)
(X)
X
X
X
X
X
X
X
X
X
yellow
flashing red
yellow and red
Alarm/Trip Lock
EC-61 Feedback Signal Monitoring
X
X
X
X
X
X
X
X
Parameter
Reference
S202
11
61
11