GE AF-650 GP PROFINET Operating Instructions Manual page 30

Table of Contents

Advertisement

How to Control the Frequenc...
Bit 04, No error/error (no trip)
Bit 04 = "0" means that the frequency converter is not in fault
mode.
Bit 04 = 1 means that there is a frequency converter error but
no trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06 = "0" means that the frequency converter is not in fault
mode.
Bit 06 = 1 means that the frequency converter is tripped, and
locked.
Bit 07, No warning/warning
Bit 07 = "0" means that there are no warnings.
Bit 07 = "1" means that a warning has occurred.
Bit 08, Speed reference/speed = reference
Bit 08 = "0" means that the motor is running, but that the
present speed is different from the preset speed reference. It
might, for example, be the case while the speed is being
ramped up/down during start/stop.
Bit 08 = "1" means that the present motor present speed
matches the preset speed reference.
Bit 09, Local operation/bus control
Bit 09 = "0" means that [STOP/RESET] is activated on the
control unit, or that Local control in F-02 Operation Method is
selected. It is not possible to control the frequency converter
via serial communication.
Bit 09 = "1" means that it is possible to control the frequency
converter via the network/ serial communication.
Bit 10, Out of frequency limit
Bit 10 = "0", if the output frequency has reached the value in
F-18 Motor Speed Low Limit [RPM] or F-17 Motor Speed High
Limit [RPM].
Bit 10 = "1" means that the output frequency is within the
defined limits.
Bit 11, No operation/in operation
Bit 11 = "0" means that the motor is not running.
Bit 11 = "1" means that the frequency converter has a start
signal or that the output frequency is greater than 0Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12 = "0" means that there is no temporary over
temperature on the inverter.
Bit 12 = "1" means that the inverter has stopped because of
over temperature, but that the unit has not tripped and will
resume operation once the over temperature stops.
PROFINET Operating Instruction
Bit 13, Voltage OK/limit exceeded
Bit 13 = "0" means that there are no voltage warnings.
Bit 13 = "1" means that the DC voltage in the frequency
converters intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14 = "0" means that the motor current is lower than the
torque limit selected in F-40 Torque Limiter (Driving) or
F-41 Torque Limiter (Braking).
Bit 14 = "1" means that the torque limit in F-40 Torque Limiter
(Driving) and F-41 Torque Limiter (Braking) has been
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15 = "0" means that the timers for motor thermal
protection and electronic overload protection, respectively,
have not exceeded 100%.
Bit 15 = "1" means that one of the timers has exceeded
100%.
6
6
29