Parameters

8 Parameters

8.1 Parameter Group O-## Communication and Option

O-01 Control Site
Option:
Function:
The setting in this parameter overrides
the settings in O-50 Coasting Select to
O-56 Preset Reference Select.
[0]
Digital and
Control by using both digital input and
*
ctrl.word
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword only
Control by using control word only.
O-03 Control Word Timeout Time
Range:
Function:
1.0 s
[0.1 -
Enter the maximum time expected to pass
*
18000.0 s]
between the reception of two consecutive
messages. If this time is exceeded, it
indicates that the serial communication has
stopped. The function selected in
O-04 Control Word Timeout Function will then
be carried out. The time-out counter is
triggered by a valid control word.
O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates when
the control word fails to be updated within the time period
specified in O-03 Control Word Timeout Time.
Option:
Function:
[0]
Off
Resumes control via serial bus (network or
*
standard) using the most recent control
word.
[1]
Freeze output Freezes output frequency until communi-
cation resumes.
[2]
Stop
Stops with auto restart when communication
resumes.
[3]
Jogging
Runs the motor at JOG frequency until
communication resumes.
[4]
Max. speed
Runs the motor at maximum frequency until
communication resumes.
[5]
Stop and trip
Stops the motor, then resets the drive in
order to restart: via the network, via the reset
button on the keypad or via a digital input.
[7]
Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
time-out. If communication resumes causing
the time-out situation to disappear, O-05 End-
of-Timeout Function defines whether to
resume the set-up used before the time-out
PROFINET Operating Instruction
O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates when
the control word fails to be updated within the time period
specified in O-03 Control Word Timeout Time.
Option:
[8]
Select setup 2 See [7] Select setup 1
[9]
Select setup 3 See [7] Select setup 1
[10] Select setup 4 See [7] Select setup 1
[26] Trip
NOTE
The following configuration is required in order to change
the set-up after a time-out:
Set K-10 Active Set-up to [9] Multi set-up and select the
relevant link in K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option:
[0]
Hold set-up Retains the set-up selected in O-04 Control
[1]
Resume set-
*
up
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been
selected in O-05 End-of-Timeout Function.
Option:
[0]
Do not reset Retains the set-up specified in O-04 Control
*
[1]
Do reset
Function:
or to retain the set-up endorsed by the time-
out function.
Function:
Select the action after receiving a valid control
word following a time-out. This parameter is
active only when O-04 Control Word Timeout
Function is set to [Set-up 1-4].
Word Timeout Function and displays a warning,
until O-06 Reset Control Word Timeout toggles.
Then the drive resumes its original set-up.
Resumes the set-up active prior to the time-out.
Function:
Word Timeout Function, following a control
word time-out.
Returns the drive to the original set-up
following a control word time-out. The drive
performs the reset and then immediately
reverts to the Do not reset [0] setting