GE AF-650 GP PROFINET Operating Instructions Manual page 37

Table of Contents

Advertisement

Parameters
O-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed network. Only the selections valid
for the network installed in slot A will be visible in the keypad
display.
Option:
[0]
*
[1]
[5]
O-13 Configurable Status Word STW
Option:
[0]
No function
[1]
Profile Default Function corresponds to the profile default
*
O-50 Coasting Select
Option:
8
8
[0]
Digit
Input
[1]
Bus
[2]
Logic
AND
[3]
Logic OR
*
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital
input) and/or via the network.
Option:
[0]
[1]
[2]
[3]
*
O-52 DC Brake Select
Option:
[0]
Digit Input ActivatesDC Brake command via a digital input.
[1]
Bus
[2]
Logic AND ActivatesDC Brake command via the network/
36
PROFINET Operating Instruction
Function:
Drive Profile
PROFIdrive profile
ODVA
Function:
This parameter enables configuration of bits
12 – 15 in the status word.
selected in O-10 Control Word Profile.
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the network.
Activates Coast command via a digital input.
Activates Coast command via the serial
communication port or network option module.
Activates Coast command via the network/serial
communication port, AND additionally via one of
the digital inputs.
Activates Coast command via the network/serial
communication port OR via one of the digital
inputs.
Function:
Digital Input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the network.
ActivatesDC Brake command via the serial
communication port or network option module.
serial communication port, AND additionally via
one of the digital inputs.
O-52 DC Brake Select
Option:
Function:
[3]
Logic OR
ActivatesDC Brake command via the network/
*
serial communication port OR via one of the
digital inputs.
O-53 Start Select
Option:
Function:
Select control of the drive start function via the
terminals (digital input) and/or via the network.
[0]
Digit
Activates Start command via a digital input.
Input
[1]
Bus
Activates Start command via the serial communi-
cation port or network option module.
[2]
Logic
Activates Start command via the network/serial
AND
communication port, AND additionally via one of
the digital inputs.
[3]
Logic OR
Activates Start command via the network/serial
*
communication port OR via one of the digital
inputs.
O-54 Reversing Select
Option:
Function:
[0]
Digital
Select control of the drive reverse function via
Input
the terminals (digital input) and/or via the
network.
[1]
Bus
Activates the Reverse command via the serial
communication port or network option module.
[2]
Logic AND
Activates the Reverse command via the
network/serial communication port, AND
additionally via one of the digital inputs.
[3]
Logic OR
Activates the Reverse command via the
*
network/serial communication port OR via one
of the digital inputs.
O-55 Set-up Select
Option:
Function:
Select control of the drive set-up selection via the
terminals (digital input) and/or via the network.
[0]
Digit
Activates the set-up selection via a digital input.
Input
[1]
Bus
Activates the set-up selection via the serial
communication port or network option module.
[2]
Logic
Activates the set-up selection via the network/
AND
serial communication port, AND additionally via
one of the digital inputs.
[3]
Logic OR
Activate the set-up selection via the network/
*
serial communication port OR via one of the
digital inputs.

Advertisement