Warnings and Alarms

11 Warnings and Alarms

11.1 Status Messages

11.1.1 Warnings/Alarm Messages

A warning or an alarm is signalled by the relevant LED on the
front of the frequency converter and indicated by a code on
the display.
A warning remains active until its cause is no longer present.
Under certain circumstances operation of the motor may still
be continued. Warning messages may be critical, but are not
necessarily so.
In the event of an alarm, the frequency converter will trip.
Alarms must be reset to restart operation once their cause
has been rectified.
This may be done in three ways:
By using the [RESET] control button on the keypad
control panel
Via a digital input with the "Reset" function
Via serial communication/optional network
NOTE
After a manual reset using the [RESET] button on the keypad,
the [AUTO] button must be pressed to restart the motor.

11.1.2 Alarm List

No.
Description
1
10 Volts low
2
Live zero error
3
No motor
4
Mains phase loss
5
DC link voltage high
6
DC link voltage low
7
DC over-voltage
8
DC under voltage
9
Inverter overloaded
10
Motor Electronic OL over temperature
11
Motor thermistor over temperature
12
Torque limit
13
Over Current
14
Earth Fault
15
Hardware mismatch
16
Short Circuit
17
Control word time-out
22
Hoist Mech. Brake
23
Internal Fan Fault
24
External Fan Fault
PROFINET Operating Instruction
If an alarm cannot be reset, the reason may be that its cause
has not been rectified, or the alarm is trip-locked (see also
Table 11.1).
Alarms that are trip-locked offer additional protection,
meaning that the mains supply must be switched off before
the alarm can be reset. After being switched back on, the
frequency converter is no longer blocked and may be reset
as described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the
automatic reset function in H-04 Auto-Reset (Times) (Warning:
automatic wake-up is possible!)
If a warning and alarm is marked against a code in Table 11.1,
this means that either a warning occurs before an alarm, or
that you can specify whether it is a warning or an alarm that
will be displayed for a given fault.
This is possible, for instance, in F-10 Electronic Overload . After
an alarm or trip, the motor carries on coasting, and the alarm
and warning flash. Once the problem has been rectified, only
the alarm continues flashing until the frequency converter is
reset.
Warning
Alarm/Trip
X
(X)
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
X
X
Alarm/Trip Lock
AN-01 Live Zero Timeout Function
H-80 Function at Stop
(X)
SP-12 Function at Line Imbalance
F-10 Electronic Overload
F-10 Electronic Overload
X
X
X
X
O-04 Control Word Timeout Function
SP-53 Fan Monitor
11
Parameter
Reference
59
11