How to Configure the System

5.3 Configure the Frequency Converter

5.3.1 Drive Parameters

Pay particular attention to the following parameters when
configuring the frequency converter with a PROFINET
interface.
K-40 [Hand] Button on Keypad. If the Hand button
on the frequency converter is activated, control of
the drive via the PROFINET interface is disabled
After an initial power up the frequency converter
will automatically detect whether a network option
is installed in slot A, and set O-02 Control Word
Source to [Option A]. If an option is added, changed
or removed from an already commissioned drive, it
will not change O-02 Control Word Source but enter
Trip Mode, and the drive will display an error
O-10 Control Word Profile. Choose between the GE
Drive Profile and the PROFIdrive profile
O-50 Coasting Select to O-56 Preset Reference Select.
Selection of how to gate PROFINET control
commands with digital input command of the
control module.
NOTE
When O-01 Control Site is set to [2] Control word only, then
the settings in O-50 Coasting Select to O-56 Preset Reference
Select will be overruled, and all act on Bus-control.
O-03 Control Word Timeout Time to O-05 End-of-
Timeout Function. The reaction in the event of a
network time out is set via these parameters
EN-00 IP Address Assignment
EN-08 Host Name