Warning 34 Appears Even Though Communication Is Established; Will Not Respond To Control Signals - GE AF-650 GP PROFINET Operating Instructions Manual

Table of Contents

Advertisement

Troubleshooting
10.1.3 Warning 34 Appears even though
Communication is Established
If the master is in stop mode Warning 34 will appear. Check
that the master is in run mode.

10.1.4 Will Not Respond to Control Signals

Check 1: Is the Control word valid?
If bit 10=0 in the Control word, the drive will not accept the
Control word.
Check 2: Is the relationship between bits in the Control word
and the terminal I/Os correct?
Check the logical relationship in the drive.
Define the desired logical relationship in O-50 Coasting Select
to O-56 Preset Reference Select according to the following
range of options. Select the Drive control mode, digital input
and/or serial communication, using O-50 Coasting Select to
O-56 Preset Reference Select.
The tables below show the effect upon the frequency
converter of a coast command for the full range of
O-50 Coasting Select settings.
The effect of control mode upon the function of
O-50 Coasting Select, O-51 Quick Stop Select and O-52 DC
Brake Select is as follows:
If Digital input [0] is selected, the terminals will control the
Coast and DC Brake functions.
NOTE
Please note that Coasting, Quick Stop and DC brake
functions are active for logic 0.
Digital input [0]
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
Coast/DC brake/Q-Stop
1
0
No Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
PROFINET Operating Instruction
If Serial communication [1] is selected, commands will be
activated only when given via serial communication.
Serial communication [1]
Terminal
0
0
1
1
If Logic AND [2] is selected, both signals must be activated to
perform the function.
Logic AND [2]
Terminal
0
0
1
1
If Logic OR [3] is selected, activation of one signal will
activate the function.
Logic OR [3]
Terminal
0
0
1
1
The effect of control mode upon the function of O-53 Start
Select and O-54 Reversing Select:
If Digital input [0] is selected, the terminals will control the
start and reversing functions
Digital input [0]
Terminal
0
0
1
1
If Serial communication [1] is selected, commands will be
activated only when given via serial communication.
Serial communication [1]
Terminal
0
0
1
1
Bit 02/03/04
Function
0
Coast/DC brake/Q-Stop
1
No Coast/DC brake/Q-Stop
0
Coast/DC brake/Q-Stop
1
No Coast/DC brake/Q-Stop
Bit 02/03/04
Function
0
Coast/DC brake/Q-Stop
1
No Coast/DC brake/Q-Stop
0
No Coast/DC brake/Q-Stop
1
No Coast/DC brake/Q-Stop
Bit 02/03/04
Function
0
Coast/DC brake/Q-Stop
1
Coast/DC brake/Q-Stop
0
Coast/DC brake/Q-Stop
1
No Coast/DC brake/Q-Stop
Bit 06/15
Function
0
Stop/Anti-clockwise
1
Stop/Anti-clockwise
0
Start/Clockwise
1
Start/Clockwise
Bit 02/03/04
Function
0
Stop/Anti-clockwise
1
Start/Clockwise
0
Stop/Anti-clockwise
1
Start/Clockwise
10
10
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Af-600 fp profinetAf-650 gpAf-600 fp

Table of Contents