6.5 GE Drive Control Profile

6.5.1 Control Word according to Drive
Profile (CTW)
To select GE Drive protocol in the control word, O-10 Control
Word Profile must be set to GE Drive protocol [0]. The control
word is used to send commands from a master (PLC or PC) to
a slave (frequency converter).
Please refer to 9 Application Examples for an example of a
control word message using PPO type 3.
Bit
Bit value = 0
00
Reference value
01
Reference value
02
DC brake
03
Coasting
04
Quick stop
05
Hold output frequency
06
Accel/Decel stop
07
No function
08
No function
09
Ramp 1
10
Data invalid
11
No function
12
No function
13
Parameter set-up
14
Parameter set-up
15
No function
Explanation of the Control Bits
Bits 00/01 Reference value
Bits 00 and 01 are used to choose between the four
reference values, which are pre-programmed in C-05 Multi-
step Frequency 1 - 8 according to Table 6.1:
NOTE
In O-56 Preset Reference Select a selection is made to define
how Bit 00/01 gates with the corresponding function on the
digital inputs.
Programmed
Parameter
ref. value
1
C-05 Multi-step
Frequency 1 - 8 [0]
2
C-05 Multi-step
Frequency 1 - 8 [1]
3
C-05 Multi-step
Frequency 1 - 8 [2]
4
C-05 Multi-step
Frequency 1 - 8 [3]
PROFINET Operating Instruction
Bit value = 1
external selection lsb
external selection msb
Accel/Decel
No coasting
Accel/Decel
Use Accel/Decel
Start
Reset
Jog
Accel/Decel 2
Data valid
Relay 01 active
Relay 04 active
selection lsb
selection msb
Reverse
Bit 01
Bit 00
0
0
0
1
1
0
1
1
Bit 02, DC brake
Bit 02 = 0 leads to DC braking and stop. Braking current and
duration are set in B-01 DC Brake Current and B-02 DC Braking
Time. Bit 02 = 1 leads to ramping.
Bit 03, Coasting
Bit 03 = 0 causes the frequency converter to immediately "let
go" of the motor (the output transistors are "shut off"), so
that it coasts to a standstill.
Bit 03 = 1 enables the frequency converter to start the motor
if the other starting conditions have been fulfilled.
NOTE
In O-50 Coasting Select a selection is made to define how Bit
03 gates with the corresponding function on a digital input.
Bit 04, Quick stop
Bit 04 = 0 causes a stop, in which the motor speed is ramped
down to stop via C-23 Quick Stop Decel Time.
Bit 05, Hold output frequency
Bit 05 = 0 causes the present output frequency (in Hz) to
freeze. The frozen output frequency can then be changed
only by means of the digital inputs (E-01 Terminal 18 Digital
Input to E-06 Terminal 33 Digital Input) programmed to Speed
up and Speed down.
NOTE
If Freeze output is active, the frequency converter can only be
stopped by the following:
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (E-01 Terminal 18 Digital Input to
E-06 Terminal 33 Digital Input) programmed to DC
braking, Coasting stop or Reset and coasting stop.
Bit 06, Ramp stop/start:
Bit 06 = 0 causes a stop, in which the motor speed is ramped
down to stop via the selected ramp down parameter.
Bit 06 = 1" permits the frequency converter to start the
motor, if the other starting conditions have been fulfilled.
NOTE
In O-53 Start Select a selection is made to define how Bit 06
Ramp stop/start gates with the corresponding function on a
digital input.
Bit 07, Reset
Bit 07 = "0" does not cause a reset. Bit 07 = "1" causes the
reset of a trip. Reset is activated on the signals leading edge,
i.e. when changing from logic "0" to logic "1".
6