Dimensions and weight
Ensure that space is available in a rack that is capable of supporting the node.
Additional space requirements
Ensure that space is also available in the rack for the following additional space
requirements around the node.
Maximum heat output of each SAN Volume Controller 2145-CF8
node
The node dissipates the following maximum heat output.

Maximum heat output of each 2145 UPS-1U

The 2145 UPS-1U dissipates the following maximum heat output.

Redundant ac-power environment requirements

Ensure that your physical site meets the installation requirements for the
redundant ac-power switch.
The redundant ac-power switch requires two independent power sources that are
provided through two rack-mounted power distribution units (PDUs). The PDUs
must have IEC320-C13 outlets.
Table 8. Dimensions and weight
Height
Width
43 mm
440 mm
(1.75 in.)
(17.32 in.)
Table 9. Additional space requirements
Location
Left side and right side
Back
Table 10. Maximum heat output of each SAN Volume Controller 2145-CF8 node
Model
SAN Volume Controller 2145-CF8
SAN Volume Controller 2145-CF8 plus
solid-state drives (SSDs)
Table 11. Maximum heat output of each 2145 UPS-1U
Model
Maximum heat output of 2145 UPS-1U
during normal operation
Maximum heat output of 2145 UPS-1U
during battery operation
Depth
559 mm
(22 in.)
Additional space
requirements
Minimum: 50 mm (2 in.)
Minimum: 100 mm (4 in.)
Heat output per node
160 W (546 Btu per hour)
210 W (717 Btu per hour)
Heat output per node
10 W (34 Btu per hour)
100 W (341 Btu per hour)
Appendix B. SAN Volume Controller physical installation planning
Maximum weight
10.1 kg
(22 lb)
Reason
Cooling air flow
Cable exit
43