2 Wing nut
5. Select the holes in the rail where you want to position the 2145 UPS-1U.
Note: The bottom flange of the support rail must align with the EIA mark on
the rack.
6. Using two M6 × 10 screws ( 1 in Figure 10) and two clip nuts 2 , attach the
rail to the rear of the rack. The customer's rack might be different than the one
shown here, and if so, might require different clip nuts or fasteners.
1
Figure 10. Securing the rear rail on the 2145 UPS-1U
7. Install two clip nuts ( 2 and 3 in Figure 11) to the front of the rack, then
attach the rail using just one M6 x 10 screw in the bottom mounting hole 1 .
Figure 11. Securing the front rail on the 2145 UPS-1U
8. Repeat steps 6 and 7 for the other rail.
9. Tighten the assembly wing nuts on both rail assemblies.

Installing the 2145 UPS-1U in the rack

After you have completed the preparation procedures, you are ready to install the
2145 UPS-1U in the rack.
2
Chapter 2. Installing the SAN Volume Controller 2145-CF8 hardware
17