Maintenance; Maintenance Schedule - Waterous HLU Series Installation, Operation And Maintenance Manual

Fire pump
Table of Contents

Advertisement

Safety
Introduction

Maintenance Schedule

Perform the following procedures at the recommended intervals at a minimum. Environmental conditions determine the maintenance intervals. Inspect the
components frequently and create a maintenance schedule suitable to your application and environmental conditions. Replace wear components with equivalent
components.
Operation
Operation
Clean the intake strainer
Check the pedestal oil level
Verify operation
Change the pedestal oil
Inspect the mounting hardware
Product Overview
Before Initial
Before Initial
Weekly
Weekly
Operation
Operation
X
X
X
Installation
Monthly
Monthly
12 Months
12 Months
Comment
Comment
More or less often as determined by usage, and the water
quality used.
Replace strainer cover O-ring—1-7/8 x 2-1/8 inches.
X
Verify the pneumatic actuator operation.
X
SAE 10W-30—standard or synthetic oil is acceptable
X
|