3.2 Connection of Thermocouple Multi-analog Input Unit

3.2.2 For Voltage Input

Wiring Diagram and Internal Circuit Diagram
Terminal layout
(Note 1)
Do not connect anything to N.C terminals.
● Use double-core twisted-pair shielded wires. It is recommended to ground them. However,
depending on the conditions of the external noise, it may be better not to ground the shielding.
● Do not have the analog input wiring close to AC wires, power wires, or load line from a device
other than PLC. Also, do not bundle it with them.

3.2.3 For Current Input

Wiring Diagram and Internal Circuit Diagram
In case of the current input, connect In terminals each other.
3-6