Creating Programs
4.5 I/O Conversion Characteristics
4.5.1 Input Conversion Characteristics (Voltage Range)
-10V to +10V DC input
Conversion characteristic
(Note 1): In the analog input unit Ver.1.1 or earlier or the analog I/O unit, a digital conversion value equivalent to the
analog input of approx. 2 V is saved in the device (WX), for the channels to which no input is connected. The
analog input unit Ver.1.2 or later are equivalent to approx. 0V.
-5V to +5V DC input (14-bit mode only)
Conversion characteristic
(Note 1): In the analog input unit Ver.1.1 or earlier or the analog I/O unit, a digital conversion value equivalent to the
analog input of approx. 2 V is saved in the device (WX), for the channels to which no input is connected. The
analog input unit Ver.1.2 or later are equivalent to approx. 0V.
4-36
Correspondence table of A/D Conversion
values
Input voltage (V)
-10.0
-5.0
0
5.0
10.0
If the input value is out of the range
Input voltage (V)
-10V or less
10V or more
Correspondence table of A/D Conversion
values
Input voltage (V)
-5.0
-2.5
0
2.5
5.0
If the input value is out of the range
Input voltage (V)
-5V or less
5V or more
Digital value
12-bit
14-bit
-2000
-8000
-1000
-4000
0
0
1000
4000
2000
8000
Digital value
12-bit
14-bit
-2000
-8000
2000
8000
Digital value
14-bit
-8000
-4000
0
4000
8000
Digital value
14-bit
-8000
8000