Installation Of The Fr-A800 - Mitsubishi Electric FATEC FR-A800 Manual

Inverter school text, inverter trouble shooting course
Hide thumbs Also See for FATEC FR-A800:
Table of Contents

Advertisement

9
REPLACEMENT PROCEDURE
9.3

Installation of the FR-A800

(1) Install the FR-A800 to the enclosure.
Since the installation size of 280K model or lower of the FR-A800 inverter is the same as that of
the FR-A700, the FR-A800 can be installed as it is in the mounting hole of the FR-A700.
(2) Open the wiring cover and route the main circuit wires.
(3) Perform the control circuit wires.
By using the option FR-A8TAT, the control circuit terminal block of the FR-A700 series inverter
(Leave the cables connected on the terminal block.) can be installed as it is in FR-A800.
1) Loosen the two installation screws at the both sides of the control circuit terminal block of the
800 series inverter. (These screws cannot be removed.)
Slide down the control circuit terminal to remove it.
Loosen
the screws.
2) Install the control circuit terminal block attachment. Be careful not to bend the pins of the
inverter control circuit connector, and fix it by the installation screws supplied with the
product. (Tightening torque: 0.33 to 0.4 N m)
3) Install the control circuit terminal block of the 700 series inverter. Be careful not to bend the
pins of A8TAT control circuit connector. Fix the control circuit terminal block by the installation
screws of the control circuit terminal block. (Tightening torque: 0.33 to 0.4 N m)
9.3 Installation of the FR-A800
9
Fix it with
the screws.
Fix it with
the screws.
 147

Advertisement

Table of Contents
loading