REPLACEMENT PROCEDURE
(6) Parameters converted for the FR-A800 are listed on the [Setting Value] column.
(7) Click [PU] to change the operation mode to PU.
(8) Check and write down the setting values of E400 (Pr.77), D000 (Pr.79).
When E400 (Pr.77) is "1", change the setting values of E400 (Pr.77) to "0".
When D000 (Pr.79) is other than "0 or 1", change the setting values of D000 (Pr.79) to "0".
To change a setting value, click the target value on the [Setting Value] column.
(9) Check that the computer is online. (Click
ONLINE.)
on the "tool menu bar" to switch the condition to
9.2 Setting the parameter