Parameter assignment
8.6 Output (4.)
8.6.3

Unit (4.1.2.)

Engineering unit to be displayed with the output value.
Options
8.6.4

Filter time constant (FILT TIME) (4.1.3.)

The time constant for the damping filter. The engineering unit is always in seconds. (This is
an exponential filter: when a change occurs at the input, the output will be at 63.2% of the
change in one time constant, and will be at full change after 5 time constants.)
Values
8.6.5

Function (CHANNEL) (4.1.4.)

Used to select between the different level block outputs: Level, or Distance. For an
illustration, see Transducer Block function groups (Page 161).
Options
8.6.6

Batch information (BATCH) (PROFIBUS PA only)

These 4 parameters are intended to be used in Batch Applications conforming to IEC 61512
Part 1 (ISA S88). Other applications do not require these values, which are only stored in the
Function Block.
96
percent
user-defined
linear
default: M
Range: 0 to 300 s
Default: 10 s
PV
Primary Value - Level
SV1
Secondary Value 1 - Level
SV2
Secondary Value 2 - Distance (value in sensor units)
%
TEXT
M, CM, MM, FT, IN
Operating Instructions, 10/2021, A5E42035355-AB