Installing/mounting

4.2 Mounting location

NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper
mounting.
• Before installing ensure there is no visible damage to the device.
• Make sure that process connectors are clean, and suitable gaskets and glands are used.
• Mount the device using suitable tools. Refer to the information in Technical
4.2
Mounting location
• Provide easy access for viewing the display and programming via the handheld
programmer.
• Provide an environment suitable to the housing rating and materials of construction.
• Provide a sun shield if the device is mounted in direct sunlight.
20
specifications (Page 125).
ambient temperature max. +65 °C (+149 °F)
flange temperature
process temperature max. +200 °C (+392 °F)
Operating Instructions, 10/2021, A5E42035355-AB