Condensed Mode Diagnosis - Siemens SITRANS LR460 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR460:
Table of Contents

Advertisement

D.10

Condensed mode diagnosis

Hex values
0x01000000
0x02000000
0x04000000
0x08000000
0x10000000
0x20000000
0x40000000
0x80000000
0x00080000
0x00100000
0x00200000
0x00400000
0x00800000
0x00010000
0x00020000
0x00040000
0x00080000
0x80000000
R indicates the message remains active as long as the reason for the message exists. A
a)
indicates the message will automatically reset after 10 seconds.
SITRANS LR460
Operating Instructions, 10/2021, A5E42035355-AB
Condensed Mode Diagnosis
Byte
Bit
0
Electronics failure
1
Mechanical failure
2
Motor Temperature too high
3
Electronics temperature too high
4
Memory error
0
5
Measurement failure
6
Device not initialized (no calibration)
7
Self calibration failed
3
New startup carried out (Warm Start)
4
Restart carried out (Cold Start)
5
Maintenance required
6
Reserved for use within the PNO
2
Set to 1 (one), if the Ident_Number of the run-
7
ning cyclic data transfer and the value of Physical
Block IDENT__NUMBER_SELECTOR parameter are
different.
0
Failure of the device or armature
1
Maintenance demanded
2
Device is in function check mode, or simulation,
or under local control e.g. maintenance
3
The process conditions do not allow the return of
3
valid values. (Set if a value has the quality Uncer-
tain - Process related, no maintenance or Bad -
Process related, no maintenance.)
4 to 7
Reserved for use within the PNO
4
0 to 6
Reserved for use within the PNO
7
0: There is no more information available
1: More diagnosis information is available in
DIAGNOSIS_EXTENSION
Communications via PROFIBUS PA
D.10 Condensed mode diagnosis
Description
Indication class
a)
R
R
R
R
R
R
R
R
R
R
R
A
A
R
R
R
R
155