Model 5100-02-IT Combustible Gas Sensor Module
Gas Factor Example
S.P. Function - Gas Factor Adjust
Select [E] to select or
number and press [E]
Acknowledgement of new Gas Factor Value
4-20 mA Adjustment Example
S.P. Function - Calib Adjust
Use
or
keys to select 4 mA or 20mA
Selects 4 mA
Momentary Acknowledge of new Set Point
S.P. Function - Calib Adjust
S.P. Function - Output during Calibration Adjust
Use
or
keys to select Track, Zero, C1.50mA, C4.00mA
Track = Output during calibration tracks the calibration gas,
Zero = Output is Zero during calibration,
C1.50mA = Output during calibration is 1.50 mA, C4.00mA =
Output during calibration is 4.0 mA
* = Current selection
S.P. Function - Calib Adjust
S.P. Function - output during Trouble Alarm
Current Valve 2.5mA for Trouble
S.P. Function - User Selectable mA Valve
Use
or
keys to select mA Valve between 0.5
and 0.7mA
Selctd 1.75mA for volume during trouble
RS-485 Adjustment Example
S.P. Function - RS-485 Address Adjust
Use
or
keys to enter new address
New address selected
S.P. Function - RS-485 Address Adjust
S.P. Function - RS-485 Baud Rate Adjust
Press [E] to select or [ ] or [ ] to select another
Table 4-3B
Set-Up Configuration
Page: 19