Page 1
CAT.EX30-1 Stainless Steel Heat Exchanger Type Air Dryer Series IDUS Series IDUS Inlet air Model IDUS3E IDUS4E IDUS6E °C temperature Air flow capacity /mim(ANR) (300) (430) (640) Power consumption W (189) (275) (295) ( ): Previous model IDU3D/4D/6D Series IDFS Series IDFS Inlet air Model...
Model Selection Obtain the correction factor for the temperature from data A or B and the correction factor for the air pressure from data C. Temperature Data A or B = Series IDUS: Data A Series IDFS: Data B Air pressure Data C = Calculate corrected air flow by using A or B and C.
Page 3
Stainless Steel Heat Exchanger Type IDUS Series 3E, 4E, 6E How to Order Model Voltage Options IDUS Air compressor Refrigerant Model Voltage 2.2kW Single phase, 240VAC (50Hz) 3.7kW R134a Single phase, 220VAC (50Hz) 5.5kW Option With anti With motor With cool With heavy duty With corrosive...
Page 4
IDUS Series Standard Specifications/Models Model IDUS3E IDUS4E IDUS6E Specification Note 2) /min (ANR) Air flow rate Operating pressure Inlet air temperature Ambient temperature Pressure dew point Compressed air Working fluid Inlet air pressure 0.15 to 1.0 2 to 80 Inlet air temperature Ambient temperature 2 to 40 (Relative humidity of 85% or less) Single phase, 220VAC (50Hz), 240VAC (50Hz)
Page 5
IDUS Series Stainless Steel Heat Exchanger Type Air Dryer 3E, 4E, 6E IDUS Evaporation thermometer Illumination switch Draft air outlet Power cord Air outlet outlet Air inlet Draft air inlet Model Port size IDUS3E Rc 1/2 IDUS4E Rc 1/2 IDUS6E Rc 3/4 Note: The diagram above is drawn base on IDUS3E dimension with scale 1:6...
Page 6
Stainless Steel Heat Exchanger Type IDFS Series 6E, 8E, 11E How to Order Voltage Options Model IDFS Air compressor Refrigerant Model Voltage 5.5kW Single phase, 240VAC (50Hz) 7.5kW R134a Single phase, 220VAC (50Hz) 11kW Option With anti With motor With cool With heavy duty With corrosive...
Page 7
IDFS Series Stainless Steel Heat Exchanger Type Air Dryer Standard Specifications/Models Model IDFS6E IDFS8E IDFS11E Specification Note 2) Air flow rate /min (ANR) 1200 1650 Operating pressure Inlet air temperature Ambient temperature Pressure dew point Working fluid Compressed air Inlet air pressure 0.15 to 1.0 Inlet air temperature 2 to 50...
Page 8
IDFS Series 6E, 8E, 11E IDFS Evaporation thermometer Illumination switch Draft air outlet Power cord Air outlet outlet Air inlet Draft air inlet Model Port size IDFS6E Rc 3/4 IDFS8E Rc 3/4 IDFS11E Rc 3/4 Note: The diagram above is drawn base on IDFS6E dimension with scale 1:6...
IDUS/IDFS Series Option Specification Refer to pages 1 and 5 for "How to Order" of options. Option symbol Option symbol With circuit breaker With cool compressed air A circuit breaker is attached to the side of the air dryer. This saves additional The air flow with this option is lower than that of the standard dryer.
Technical Data Pressure dew point Condensed water calculation Amount of condensed water 18.2 - 3.0 = 15.2 g /m Intake air temperature C (atmospheric pressure) Air temperature (Pressure dew point) C [Example] If air at 30 C and 60% humidity is pressurized to 0.7MPa, the dew point of the air will be 62 C. ( ) If this is cooled to 25 C, the amount of condensed water generated will be 15.2g/m ) Therefore, with an air flow rate of 3m...
IDUS/IDFS Series Safety Instructions These safety instructions are intended to prevent a hazardous situation and/or equipment damage. These instructions indicate the level of potential hazard by a label of "Caution", "Warning" or "Danger". To ensure safety, be sure to observe Note 1) Note 2) ISO 4414...
Page 12
IDUS/IDFS Series Air Preparation Equipment Precautions 1 Be sure to read before handling. Precautions on Design Selection Employ a safe design so that the following type Caution of unexpected conditions will not occur. 1. Do not allow flow greater than the rated flow Warning rate.
Page 13
IDUS/IDFS Series Air Preparation Equipment Precautions 2 Be sure to read before handling. Maintenance Air Supply Warning Warning 1. Do not use with fluids other than compressed 1. If an abnormality occurs, stop the com- air. pressed air. Cleaning equipment is designed exclusively for use with com- If abnormalities such as smoke, unusual odor or unusual noise pressed air.
Page 14
IDUS/IDFS Specific Product Precautions 1 Series Air Preparation Equipment Precautions Refer to pages 12 through 14 for safety instructions and cleaning equipment precautions. Power Supply Installation Location Caution Caution Connect the power supply to the terminal block. Avoid locations where the air dryer will be in direct contact with wind and rain.
Page 15
IDUS/IDFS Specific Product Precautions 2 Series Air Preparation Equipment Precautions Refer to pages 12 through 14 for safety instructions and cleaning equipment precautions. Time Delay for Restarting Protection Circuit Caution Caution Allow at least three minutes When the air dryer is operated under the following conditions, the before restarting the dryer.
Page 16
SMC'S GLOBAL MANUFACTURING, DISTRIBUTION AND SERVICE NETWORK EUROPE EUROPE ASIA AUSTRIA SLOVAKIA THAILAND SMC Pneumatik GmbH SMC Thailand Ltd. SMC Priemyselná Automatizáciá, s.r.o. CZECH SLOVENIA NORTH AMERICA SMC Industrial Automation CZ s.r.o. SMC Industrijska Avtomatika d.o.o. DENMARK CANADA SPAIN/PORTUGAL SMC Pneumatik A/S SMC Pneumatics (Canada) Ltd.
Need help?
Do you have a question about the IDUS Series and is the answer not in the manual?
Questions and answers