Installation Instructions

12.3 Error Codes

12.3.1 9k~18k models

Number
Cause
1
Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
2
Indoor and outdoor unit communication malfunction
3
Indoor fan speed malfunction
4
Indoor room temperature sensor error
5
Evaporator coil temperature sensor error
6
Refrigerant leak detection system malfunction
7
Water level alarm malfunction
8
Dual indoor unit (twin model only) communication malfunction
9
Other twin model malfunction
10
Overload protection
11
Outdoor temperature sensor error
12
Outdoor condenser pipe sensor error
13
Discharge air temperature sensor error
14
Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
15
Outdoor fan speed (DC fan motor only) malfunction
16
Auto-lifting panel communication error
17
Auto-lifting panel malfunction
18
Auto-lifting panel is open
19
Inverter module IPM protection
20
High/Low voltage protection
21
Compressor top overheating protection
22
Outdoor low temperature protection
23
Compressor drive error
24
Mode confl ict
25
Compressor low-pressure protection
26
Outdoor IGBT sensor error
Table 11
9k~18k models do not have display to show error codes and Operation
and Timer Indicator will turn on / off and or fl ash according to above table
to show system malfunction.
3 2 |
Bosch Climate 5000 Series Four Way Cassette Ductless Split Air Conditioner / Heat Pump (06.2022)
Operation indicator fl ashes
Timer indicator
1
2
4
5
6
7
8
9
10
1
2
3
4
5
6
8
9
10
1
2
3
4
5
6
7
8
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash