12 Electrical and Refrigerant Leak Checks

12.1 Electrical Safety Checks

After installation, confi rm that all electrical wiring is installed in
accordance with local and national codes / regulations, and according
to the Installation Manual. All testing must be performed by a licensed
electrician.
Before test run
Check grounding work
Measure grounding resistance by visual detection and with grounding
resistance tester. Grounding resistance must be less than 0.1Ω.
This may not be required for some locations. Refer to local code
requirements.
During test run
Check for electrical leakage:
During the Test Run , use an electroprobe and multimeter to perform a
comprehensive electrical leakage test. If electrical leakage is detected, turn
off the unit immediately and call a licensed electrician to fi nd and resolve the
cause of the leakage.
WARNING: ELECTRICAL HAZARD
 All wiring must comply with local and national electrical
codes and must be installed by a licensed electrician.
Bosch Climate 5000 Series Four Way Cassette Ductless Split Air Conditioner / Heat Pump (06.2022)

12.2 Refrigerant Leak Checks

Perform refrigerant leak check on all joints.
Check-point of indoor unit
Check-point of outdoor unit
A: Low pressure service valve
B: High pressure service valve
C& D: Indoor unit flare nuts
Figure 60
Installation Instructions
D
B
C
A
| 31