Installation Instructions

5.3 Applicable Models : 24k - 48k

Refrigerant piping side
78cm / 30in (Suspension bolt)
84cm / 33in(Body)
95cm / 37.4in (Panel)
24-48K ceiling hole size
Figure 9
>1m / 39in
Figure 10
1 2 |
Drain hose side
>1m / 39in
>1m / 39in
>1m / 39in
Bosch Climate 5000 Series Four Way Cassette Ductless Split Air Conditioner / Heat Pump (06.2022)
L
10 - 18mm (0.4-0.7")
Drop ceiling
Figure 11
The bottom of the unit should be 10 - 18mm (0.4-0.7in) higher than the
drop ceiling. Generally, L (indicated in Fig. 10) should be half the length
of the suspension bolt or long enough to prevent the nuts from coming
off .