EE800 CURRENT OUTPUT
EE800 DIGITAL INTERFACE
configuration connector
termination resistor
MODBUS AND BACNET
HARDWARE
The bus termination shall be realized with 120 Ohm resistor by using the switch on the board.
Very important:
For proper function the power supply must be strong enough to ensure supply voltage within the specified range (see technical
data) at any time and at all devices in the bus. This is particularly relevant when using long and thin cables which can cause high
voltage drop; please note that a single EE800 draws a peak current of 150 mA.
ADDRESS SETTINGS
ADDRESS SWITCH
1
0
0 0 0 0 0
0 0
0
ADDRESS SWITCH
1
0
1 1 0 1 0
0 0
0
BACNET INFOS
Please see PICS (Product Implementation Conformance Statement) - available at www.epluse.com/EE800)
configuration
connector
* Very important: for failure-free operation and performance according to the specs the supply GND and the
Connection on the electronics board.
Screw terminals appropriate for daisy-chain wiring
Address setting via EE-PCS Product Configuration Software:
All switches at position 0 → address has to be set via configuration software
(factory setting: 241...Modbus / 3...BACnet).
Example: Address is set via configuration software.
Address setting via DIP switch:
Setting the DIP switch to any other address than 0 overwrites the address
set via configuration software.
Example: Address set to 11 (=00001011 binary).
Output: 0-5 V
Output: 0-5 V
*
*
Output: 4-20 mA
Output: 4-20 mA
measurement GND must be wired separately.
0-10 V
0-10 V