Configuration Of A Fail-Safe System With Simatic S7-1500Hf - Siemens SIMATIC S7-1500 System Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Configuration example
Optional load current supply
CPU (with two synchronization modules, connected underneath, not visible in the diagram)
Mounting rail with integrated DIN rail profile
Redundancy connections (fiber-optic cables)
PROFINET cable
Figure 4-15  S7‑1500H configuration example
4.2.3

Configuration of a fail-safe system with SIMATIC S7-1500HF

Configuration
Fail-safe automation systems (F-systems) are used in systems with higher safety
requirements. F-systems control processes and ensure that they are in a safe state
immediately after shutdown. In other words, F-systems control processes in which an
immediate shutdown does not endanger persons or the environment. The 1518HF-4 PN CPU
is a high-availability H-CPU with integrated F-functionality (HF-CPU).
The HF-system is made up of the following components:
• Two HF-CPUs
• Two SIMATIC memory cards
• Four synchronization modules (two synchronization modules in each HF-CPU)
• Two redundancy connections (two duplex fiber-optic cables)
• IO devices with fail-safe modules
• Load current supply (optional)
You can combine fail-safe I/O modules and non-fail-safe I/O modules in the IO devices.
The HF-system (with the 1518HF-4 PN CPUs) exchanges:
• Safety-relevant data with fail-safe modules of the IO devices
• Non-safety-relevant data with non-fail-safe modules of the IO devices
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
System overview
4.2 Configuration
41