Siemens SIMATIC S7-1500 System Manual page 127

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Failure scenario
Figure 5-37  Failure of a switch in the PROFINET ring (using S7-1500R as an example)
Sequence of events
1. A switch (with additional line topology) fails in the PROFINET ring.
2. The PROFINET ring is interrupted.
3. If applicable, the redundant system selects an alternative connection to the IO devices
and
the PROFINET ring again.
4. The failure of the switch has an impact on the process as the IO devices in the additional
line topology can no longer be accessed.
If the failed inputs and outputs have an important function in the system, their failure can
have a critical impact on the process.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Primary CPU
Backup CPU
PROFINET cable (redundancy connections, PROFINET ring)
IO device ET 200MP
IO device ET 200SP
Switch → failed
IO device ET 200SP
HMI device
over the backup CPU. This allows the redundant system to access all IO devices in
Application planning
5.5 Failure scenarios
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500rSimatic s7-1500h

Table of Contents