Introduction
The supply voltage is supplied over a 4-pin connector at the front of or bottom of the R/H-
CPU.
Connection for supply voltage (X80)
The connections of the 4-pole connector have the following meaning:
Figure 7-3  Connection for supply voltage
The cable connector enables you to loop the supply voltage uninterrupted, even when it is
unplugged.
Requirements
• Only wire the cable connector when the supply voltage is turned off.
• Follow the wiring rules (Page 174).
Tool-free connection of cables: multi-wire (stranded), with end sleeve or ultrasonic compressed
To connect a wire without tools, follow these steps:
1. Strip 8 to 11 mm of the wires.
2. Seal or crimp the wire with end sleeves.
3. Insert the cable into the push-in terminal as far as it will go.
4. Push the wired connector into the socket of the CPU.
Tools required
3 to 3.5 mm slotted-head screwdriver
176
+24 V DC of the supply voltage (current limited to 10 A)
Ground of the supply voltage (current limited to 10 A)
Ground of the supply voltage for loop-through
+24 V DC of the supply voltage for loop-through
Spring opener (one spring opener per terminal)
S7-1500R/H redundant system