Commissioning
11.3 Commissioning procedure
Procedure
Proceed as follows:
1. Right-click to select the S7-1500R/H system in the project tree.
2. Select the "Download to device" > "Hardware and software (changes only)" command
from the shortcut menu.
The "Extended download" dialog window shows the addresses of the configured CPUs in the
"Configured access nodes of..." table.
1. Select the subnet from the "Type of the PG/PC interface" drop-down lists.
2. Select the adapter at the "PG/PC interface".
3. Select the interface to which the PG/PC is connected from the "Connection to
interface/subnet" drop-down list. Alternatively, select the entry "Try all interfaces".
4. Then click on the "Start search" button.
Figure 11-4  "Extended download" dialog window (primary CPU)
The "Select target device" table shows the CPUs in the S7-1500R/H system and their roles.
The primary CPU is already selected. Requirement: You have already assigned the IP
addresses using the displays of the CPU (for example for commissioning) or over
accessible devices in STEP 7.
5. Click "Load".
NOTE
Remember the redundancy IDs of the CPUs in the configuration:
• The real CPU with redundancy ID 1 uses the project data of the top CPU in the STEP 7
project tree.
• The real CPU with redundancy ID 2 uses the project data of the bottom CPU in the STEP 7
project tree.
You read out the redundancy ID of a CPU over the display with the menu command
"Overview > Redundancy". You can find more information on assigning redundancy IDs in the
section Redundancy IDs (Page 252).
"Load preview" dialog window
If necessary, the project data is compiled before the download. You can only load project data
that is consistent and has been compiled without errors.
The "Load preview" dialog window sets out the key information on the load process to be run: