Siemens SIMATIC S7-1500 System Manual page 362

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Technical specifications
15.4 Mechanical and climatic ambient conditions
Climatic ambient conditions
The table below shows the permissible climatic environmental conditions for the SIMATIC
S7-1500R/H redundant system during operation.
Table 15-8  Climatic ambient conditions
Ambient conditions
Temperature R-
Horizontal
CPUs
mounting pos­
ition
Vertical
mounting pos­
ition
Temperature H-
Horizontal
CPUs
mounting pos­
ition
Vertical
mounting pos­
ition
Temperature vari­
ation
Relative humidity
Barometric pres­
sure
Pollutant concen­
tration
If you use the Sync Module 1 GB FO 40 km (6ES7960-1FE00-0AA5) synchronization modules in the H-CPUs, then restric­
1)
tions apply to the maximum ambient temperature.
Using the redundant S7-1500R/H system over 2000 m above sea level
Table 15-9  R/H CPUs for maximum installation altitude 5000 m
CPU designation
CPU 1513R-1 PN
362
Permissible range
from 0 to 60 °C
Article No. 6ES7513-1RL00-0AB0,
6ES7515-2RM00-0AB0:
from -30 to 60 °C
Article No. 6ES7513-1RM03-0AB0,
6ES7515-2RN03-0AB0:
from 0 to 40 °C
Article No. 6ES7513-1RL00-0AB0,
6ES7515-2RM00-0AB0:
from -30 to 40 °C
Article No. 6ES7513-1RM03-0AB0,
6ES7515-2RN03-0AB0:
from 0 to 60 °C
from 0 to 55 °C
with synchronization modules Sync
Module 1 GB FO 40 km
1)
(6ES7960-1FE00-0AA5)
from 0 to 40 °C
from 0 to 35 °C
with synchronization modules Sync
Module 1 GB FO 40 km
1)
(6ES7960-1FE00-0AA5)
10 K/h
from 10 % to 95 %
From 1140 to 795 hPa
ANSI/ISA-71.04 severity level G1; G2;
G3
Article number
6ES7513-1RL00-0AB0
6ES7513-1RM03-0AB0
Comments
To increase the service life of the display, the dis­
play switches off when the permitted operating
temperature is exceeded.
At certain temperatures, the display switches off
and on again. You can find more information in
the technical specifications in the CPU manuals.
-
Without condensation
Corresponds to an altitude of -1000 m to 2000 m.
Note the following section "Using the redundant
S7-1500R/H system over 2000 m above sea level".
-
Version
FS01 or higher 5,000 m
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Max. installation
altitude

Hide quick links: