Commissioning
11.4 Operating and system states
⑨
SYNCUP → RUN-Solo, RUN-Syncup → RUN
Transition
Description
System state trans
SYNCUP → RUN-Solo
ition
The redundant system switches from the SYNCUP system state to the RUN-Solo
system state if:
•
You execute POWER OFF for the backup CPU
or
•
The redundant system detects an error during SYNCUP that prevents
redundant operation
or
•
You set the backup CPU to STOP with the PG/PC, the display or the mode
selector.
Primary CPU oper
RUN-Syncup → RUN
ating state trans
The primary CPU switches from the RUN-Syncup operating state to the RUN
ition
operating state and continues to execute the user program.
⑩
SYNCUP → STOP, RUN-Syncup → STOP
Transition
Description
System state trans
SYNCUP → STOP
ition
The redundant system switches from the SYNCUP system state to the STOP sys
tem state if:
•
You set the primary CPU or both CPUs to STOP with the PG/PC, the display
or the mode selector.
•
SYNCUP Is aborted as a result of an error in the primary CPU or in both
CPUs.
Operating state
RUN-Syncup → STOP
transitions
The primary CPU switches from the RUN-Syncup operating state to the STOP
operating state if:
•
The primary CPU detects an error that prevents further processing
or
•
You set the primary CPU to STOP with the PG/PC, the display or the mode
selector
or
•
The redundant system processes a STOP command in the user program.
SYNCUP → STOP
The backup CPU restarts and switches to the STOP operating state after SYN
CUP aborts if:
•
SYNCUP Is aborted due to an error (for causes and remedies, see section
SYNCUP system state (Page 270))
or
•
You set the CPU to STOP with the PG/PC, the display or the mode selector.
288
Effects
This system state trans
ition does not have any
effect on data.
These operating state
transitions have no
effect on data.
Effects
This system state trans
ition does not have any
effect on data.
These operating state
transitions have no
effect on data.
S7-1500R/H redundant system