3-beam ultrasonic flowmeters
for custody transfer
of liquid hydrocarbons
ufc iii f/...eex ultrasonic flow converter
ufs iii f/...eex ultrasonic flow sensor (43 pages)
Page 2
All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written authorisation of KROHNE Messtechnik GmbH. Subject to change without notice. Copyright 2019 by KROHNE Messtechnik GmbH - Ludwig-Krohne-Str. 5 - 47058 Duisburg (Germany) www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
4.4 Analog I/O connections....................29 4.5 Serial data communication (RS 485)................30 4.6 KROHNE Care board ...................... 31 4.7 Power connection ......................32 4.8 Cabling ..........................33 4.9 Grounding ........................34 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 4
8.5 Exchange of transducers - Pressurised condition ............87 8.5.1 Transducer retraction tool....................89 8.5.2 Procedure to remove a transducer ..................90 8.6 Exchange of electronics unit ..................102 8.6.1 Field version........................102 8.7 Battery maintenance ....................105 www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
INFORMATION! The manufacturer is not liable for any damage resulting from improper use or use for other than the intended purpose. The ALTOSONIC V12 is an ultrasonic gas flowmeter for high accurate and custody transfer applications. CAUTION! High levels of CO can inhibit the operation of an ultrasonic flowmeter due to its acoustic absorption properties.
• CSA C22.2 No. 94.2 • CSA C22.2 No. 61010-1 INFORMATION! Not all country specific approvals are listed here. Please consult KROHNE in case of a specific approval that is not listed here. 1.3 Safety instructions from the manufacturer 1.3.1 Copyright and data protection The contents of this document have been created with great care.
This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. Special considerations and precautions are also described in the document, which appear in the form of icons as shown below. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
In general, devices from the manufacturer may only be installed, commissioned, operated and maintained by properly trained and authorized personnel. This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
The reflective chords that are in the centre line of the meter reflect directly on the pipe wall. Direct chords do not reflect and therefore do not require acoustic mirrors. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Figure 2-5: Converter housing 1 Power supply / RS485 compartment / Optional KROHNE Care board / Service ethernet / Logging SD card 2 Electronics / display / dip switches 3 Outputs (frequency / status / 4...20 mA) INFORMATION! If needed, ask your supplier for the optional KROHNE Care manual.
Page 14
• Frequency and status output board • Processor boards • Sensor driver board • Display module (connected to the front side of the frame, can be seen through the cover with the glass window) www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
ALTOSONIC V12 2.3 Software description The ALTOSONIC V12 contains a powerful microprocessor that controls the functions and calculations it performs. The microprocessor executes program code consisting of several modules, according to the functions it has to perform. By means of a set of parameters the software can be configured to various sizes and models of flowmeters and according to specific requirements depending of applications or customers.
Check for the correct supply voltage printed on the nameplate. Figure 2-6: Example of a ATEX nameplate Figure 2-7: Example of a IECEx nameplate Figure 2-8: Example of a CLASS I, DIV I nameplate www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 17
DEVICE DESCRIPTION ALTOSONIC V12 Figure 2-9: Example of an FM Class I Division 2 nameplate Figure 2-10: Example of a CSA nameplate 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
A coating can even be regarded as unwanted because it may wear off, which will have an impact (although minor) on the accuracy. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
In case a fork lift will be used make sure that the flowmeter is secured against rolling off the • forks, or against straps sliding off the forks. Verify local safety regulations, directives and company procedures with respect to hoisting, • rigging and transportation of (heavy) equipment. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
In this case a calculation must be made to verify that the load on the pipeline will not exceed acceptable values. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
When a flow conditioner is included in the metering run, it is strongly advised to use the same flow conditioner and inlet pipe configuration during a flow (wet) calibration (see e.g. ISO 17089 or AGA-9 for detailed requirements). 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
A pressure sensing line should be properly supported to avoid vibrations and to prevent the weight of the sensing line from applying a strain on the pressure port connection. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Another option is to thermally insulate the complete metering section including the sensors. As an option, KROHNE has also developed a sun shade specifically for the electronics. This can be ordered separately and can easily be installed as presented in the figure below.
Closing the covers is done in the reverse order. Turn the cover until the little knob on the cover is located under the interlocking device, then fasten the interlocking device. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
L,min = 2 kΩ (R is limiting resistor) L,max • Use shielded cables in order to reduce radiation from electrical interferences (EMC). Figure 4-2: Digital I/O as NPN transistor www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
One of the status outputs may be programmed to a second pulse output, having the same frequency as the first pulse output, however the phase difference can be set to either 0, 90, 180 or 270 degrees. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
C/C- will occur. Place the frequency output B/B- in series with status bit C/C- as presented in the figure shown below. Figure 4-4: Connection diagram for turbine emulation 1 Alarm www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
) / Imax (R is limiting resistor) Figure 4-5: Current output passive I INFORMATION! In the connection diagram, X = E and X- = E-. Please see sticker in the housing. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Ensure that the housing gasket is properly fitted, clean and undamaged. 4.5 Serial data communication (RS 485) Figure 4-7: Connection of serial data communication INFORMATION! For more information about Modbus, refer to Modbus protocol description and set-up on page www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
ALTOSONIC V12 4.6 KROHNE Care board If the ALTOSONIC V12 is provided with the optional KROHNE Care diagnostics board, then one Custody Transfer Modbus connection is used for the communication with this board. With this KROHNE Care board, there are some new I/O connections: •...
The protective conductor clamp or GND of the connector can be used for the shielding of the • cable. • The electronics is protected against connecting a power supply with the wrong polarity. Figure 4-9: Location of power connector www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
1 Signal output (frequency / pulse) 2 Ex d approved blind plug 3 Power supply 24 VDC 4 RS485 Modbus (optional UTP cable for KROHNE Care Expert system) 5 Signal output (frequency / pulse) WARNING! Replace any unused cable gland by an Ex-d blind plug! •...
There are two screw connection points (one M5 thread and one M4 thread) to attach a ground conductor. They can be used to connect the upstream and downstream piping to the flowmeter (Equipotential). Figure 4-11: Location of grounding connectors www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
The used power supply must be able to supply at least 3 A during the start-up of the converter. When the power is switched on, a self test is carried out (KROHNE logo is visible during the test). After that the device immediately begins measuring, and the current values are displayed.
Touching them from the side can cause incorrect operation. After 5 minutes of inactivity, there is an automatic return to measuring mode. Previously • changed data is not saved. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
1 Indicates a possible status message in the status list 2 Lock, indicating that programming is not possible 3 Actual screen 4 First measured variable in large depiction 5 Description with 3 measured values 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Graphical Page Graphical Page Graphical Page 4.1.5.1 Show Value 4.1.5.2 Graph type 4.1.5.3 Minimum 4.1.5.4 Maximum 4.1.5.5 Time 4.1.6 Status Page Status Page Status Page Status Page 4.1.6.1 Reset Errors www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Also the CPU board that holds all Custody Transfer (CT) settings can be replaced but special attention is required. After initial calibration of the ALTOSONIC V12, all CT settings are stored inside the meter (CPU board) and a dipswitch no 4 is put in the locked position.
Page 40
OPERATION ALTOSONIC V12 Figure 6-4: Sealing of nameplate www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
• Modbus • USB 7.2 Installation of the software After the software has been installed, the Windows Program menu will have an item KROHNE Custody Transfer Products with sub item KROHNE Flow Meter Configuration & Monitoring Tool. 7.3 Starting a session CAUTION! To secure reliable operation of the meter, access is limited by means of passwords.
Page 42
1. Click OK to confirm if you want to select the option as displayed or - if not - 2. Click the down button to have the other options displayed. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 43
3. Select and click the option you need. 4. Click OK to confirm. KROHNE Flowmeter Configuration and Monitoring Tool will now send a message, asking for a response from any meter that is able to communicate using the selected communication method.
Page 44
The other communication option are peer-to-peer and will request for setting up the communication link. An arrow in the most left column in the dialog box marks the meter selected to start a communication session. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 45
If the problem has been solved properly, the meter that you are looking for will be listed in the dialog box. Type your name and password in the dialog box and click OK. Figure 7-8: Login dialog box 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
. A default monitoring configuration file can be found in the software “ ” installation package. Once a monitoring configuration is loaded, the monitoring process can be started and stopped. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 47
Later it will be explained how you can do this. As a start you can select the default monitoring configuration file. A dialog box will appear, asking whether you want to start the monitoring function now: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 48
Step 5: Step 5: Step 5: Figure 7-13: Tools menu Step 6: Click “Settings”. A window “Settings” with tabbed sheets will open. Step 6: Step 6: Step 6: Figure 7-14: Settings www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
7.5 Changing and saving a monitoring configuration 7.5.1 Creating a monitoring configuration When opening the KROHNE Flowmeter Configuration and Monitoring Tool the default settings are such that a default monitoring file is loaded and that a default user view is activated. Also the KROHNE Flowmeter Configuration and Monitoring Tool will start logging directly.
Page 50
Step 3: Click “Yes” to stop the monitoring activity. INFORMATION! Note that the instrument itself will not stop measuring! Only the presentation of measuring results will be interrupted. The Monitoring Configuration dialog appears: Figure 7-17: Monitoring configuration www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 51
You can adjust the rate at which the selected data will be sent and updated: Step 11: Step 11: Click the “down”- arrow left of “Interval in sec.” Step 11: Step 11: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
(loosing your modifications) or you can save the modified configuration, this will overwrite the starting configuration (and the starting configuration will be lost). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 53
Step 3: Type a new name in the box “Filename”. Step 3: Step 3: Step 4: Step 4: Click "Save". Step 4: Step 4: Your new monitoring configuration is now saved with its new name. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Figure 7-23: File menu Step 2: Step 2: Step 2: Step 2: Click “Save Monitoring Configuration”. The monitoring configuration file used as starting point will now be replaced by the modified monitoring configuration. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
You can use this even if you already have a monitoring configuration opened and running. In that case you are asked to stop the running monitoring session. Figure 7-25: Warning for running session Click “Yes”. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 56
Step 6: Set or adjust the “Fetch Rate” to the value as required. Step 6: Step 6: Step 6: Step 7: Step 7: Click “Close” in the “Monitoring Configuration” window. Step 7: Step 7: www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 57
(if you want to keep both you have to use the “Save as…” option before you exit the program). 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
An information window as below will appear as a scroll list. The shown data is the data as currently being collected from the meter: only the values of the variables as defined in the monitoring configuration file. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
(for presenting data as a graph of one variable as a function of “ ” another variable). The name of the file defining the format of the presentation in a specific panel can be read in its upper left corner. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 60
Step 4: Open the selection list for the type of panel you want to use: click the down arrow to the Step 4: Step 4: Step 4: right of the box “Type” in the section “Upper Panel”. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Step 5: In order to have a visible grid displayed, the size of the grid (number of cells) has to be Step 5: Step 5: defined. With a right mouse click a menu will open, click the option “Add Column(s)”: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 62
“Add Row(s)”. Figure 7-33: Add Rows Step 8: Step 8: Type the number of rows in the dialogue box that appears and click OK. Step 8: Step 8: www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 63
Subitem is the array index for a variable defined as an array. Step 10: Step 10: Click the index of the array element to be displayed. Step 10: Step 10: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 64
Use the command Save Monitoring “ Configuration As.. (in File Menu) . This command stores the set up of the information sheets ” contained in User Views as well. “ ” www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Step 10: Click “Save As”. Step 10: Step 10: Step 10: Enter a name for the graphical presentation you just have created. Step 11: Step 11: Click “Save”. Step 11: Step 11: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
To obtain a report: Click “Tools” to open the Tools menu. Click “Reporting” to open the Reporting submenu. Figure 7-35: Tools > Reporting menu www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Creating a formatted report Go to "Reports & Exports > Reports > Standard parameter report". Figure 7-37: Parameter report A formatted preview of the Standard Parameter Report will be displayed: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 68
Printing a formatted report Figure 7-39: Report preview Click the button with the printer icon in the upper left of the window to get a printed copy of the report. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 69
A window opens that allows you to make a selection of the attributes to be listed for each parameter. Select the items you want to include in the exported file. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 70
• In the output dialog box that appears: specify the location where you want to store the file. • Type a unique file name for the document. • Click the button Save. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Figure 7-43: Monitoring menu When you open the “Monitoring” menu you will observe also a check mark to the left of the option “Logging” when data is actually being logged. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
“Fetch Rate” (parameter value equal to 1) or it is a fraction of the “Fetch rate” (integer parameter value 2..10). Set “Log Rate Log Rate” Log Rate Log Rate Click “Monitoring” to open the “Monitoring” menu. Click “Configure…” to open the Monitoring Configuration window. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 73
To define or select the data items to be stored in the log file: Click “Monitoring” to open the “Monitoring” menu. Click “Configure…” to open the Monitoring Configuration window. In the Monitoring Configuration window as above: Click “Select Items”. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 74
Step 3: (Variables already included in the monitoring list will have a green background colour). Step 4: Step 4: Find the variable you want to add in order to be included in the logging. Step 4: Step 4: www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 75
The size of a log file can be limited either to a maximum number of records or to a maximum time span. In the value list of the box “Switch file based on;” click either • Duration, or • Number of records 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 76
Step 1: Click the menu button “Tools” to open the Tools menu. Step 1: Step 1: Step 1: Step 2: Step 2: Click “Settings…” to open the “Settings” window below: Step 2: Step 2: www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Step 1: Click the button "File" to open the file menu. Step 1: Step 1: Figure 7-49: File menu Step 2: Step 2: Step 2: Step 2: Click the menu item “Save Flow Meter Configuration as XML file...”. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 78
Step 3: Step 3: Type a new name in the box “Filename”. Step 4: Step 4: Click "Save". Step 4: Step 4: Your new Flow Meter Configuration is now saved. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
The ALTOSONIC V12 also has on board diagnostic features that will alert the operator in case of malfunctioning. In a log file information will be stored with much more detail.
(can be used together with tool number 4) 6 Insertion for tool number 4 7 Bits in different sizes (to open the housing) 8 Slotted hexagonal wrench (for titanium transducers) 9 O-rings, nuts and capbolts www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 81
To access the transducer position that needs to be replaced use the following instructions. WARNING! The ALTOSONIC V12 is a pressurised UFM. Do not remove transducer, bolts or other pressurised parts without the garantuee that the meter is fully depressurised. INFORMATION!
Page 82
Figure 8-6: View at installed transducer 1 Hexagonal securing screw M2 2 Holes for removal of cap (epoxy transducer) INFORMATION! To remove the cap, a different tool is used for each type of transducer. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 83
• Pull the coax cable with the Ex-d plug out of the transducer. Figure 8-9: Removal of transducer nut 1 Insert the tool in the transducer nut 2 Turn tool counter clockwise to loosen the transducer nut 3 Transducer nut 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 84
When the same transducer is reused, make sure that two new O-rings are used to prevent • leakage. Figure 8-12: Installing transducer in tool 1 Put the tool on the transducer. 2 Turn the tool clockwise to attach it to the transducer. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 85
1 Put cap on tool and insert it onto the transducer 2 Carefully turn tool clockwise in small steps to tighten the cap INFORMATION! For a titanium transducer, you will need the tool with the slotted hexagonal head. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 86
After the maintenance work, make sure that no error messages are displayed on the display and / or check the correct operation with the Flow Meter Configuration and Monitoring Tool. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Make sure an electronic instrument for measuring resistance and capacitance is available, • check that it is recently calibrated and fitted with fresh batteries (or spare batteries are available. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 88
Decide which persons need to be involved in the operation, especially the ones that have to perform the job at the location of the meter, empower procedures to limit access to the area where the operation takes place only to them. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
A "U" refers to the upstream transducer and a "D" refers to the downstream transducer of an acoustic path. For an ALTOSONIC V12 six transducers (belonging to three acoustic paths) are located on one side (front) of the flowmeter. The codes and locations of these transducers are indicated in the figure below.
Page 91
Two transducers are located on the top of the ultrasonic flowmeter. The codes and locations of these transducers are indicated in the figure below. Figure 8-20: Transducers on top side of the flowmeter 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 92
• Turn the special tool counter clockwise 4 to loosen the cap from the transducer. Make sure that the cable is not twisted. Epoxy transducer Figure 8-22: Remove cap • Pull the coax cable with the connector out of the transducer. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 93
(not more than one turn) to allow the pin inside the transducer adapter to slide into the slot in the extension with M10 screw thread on top of the transducer. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 94
Make sure that the pressure sealing (O-ring) between the adapter plate and the meter body is in good shape and fitted properly, if damaged replace (size 43.0 x 3.5 mm). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 95
Turn the adapter clockwise as much as possible. INFORMATION! This should force the clearance between both plates to open to about 1 mm. • Tighten the bolts (8 pieces) with the 5 mm hexagon key. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 96
• Memorize and note this value as "Depth". Figure 8-28: Measure depth 1 Bronze fixation nut. 2 Insert ruler up to bronze fixation nut. 3 Read the depth. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 97
4 bolts M8 x 20 mm (only use grade 12.9). When properly positioned and tightened: on opposite sides, where the ends of two halves meet, the clearance should be equal, on each side approximately 3 mm. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 98
• Measure the position of the shaft relative to the tube. • Check that the shaft has moved at least 33 mm further compared to the measurement at the previous item ("Reference"). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 99
Figure 8-34: Measure position shaft 1 Read the distance. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 100
Figure 8-36: Remove tube 1 Pull tube out of ball valve. 2 Locate the front of the transducer. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 101
The removed transducer can now be detached from the transducer adapter. The adapter, the transducer fastening nut and the bronze adapter fastening nut are available to be used to continue the operation to re-install a new transducer. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
• Release the fasteners that prevent opening of the Ex d enclosure with a 2.5 mm Allen key. • Turn the display cover of the electronics compartment counter clockwise 1. • Use a screwdriver to pull the pullers a bit out 2. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 103
Figure 8-40: Use pullers to partially pull the electronic unit out of the housing • Pull the two metal pullers at the left and right of the display and partially pull out the electronics unit. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 104
• Screw the electronics unit back to the housing. • Re-install the display and make sure not to kink the display's flat ribbon cable. • Replace cover and tighten by hand. • Connect power. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
• such dangerous substances, to enclose a certificate with the device confirming that it is safe to handle and stating the • product used. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
The user must dispose of the WEEE to a designated collection point for the recycling of WEEE or send them back to our local organisation or authorised representative. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
The trajectory of the sound wave is called the acoustic path. A chord is the direct path crossing the pipe from one side to the opposite side. Using reflection, an acoustic path can consist of two or more chords. The name ALTOSONIC V12 is related to its design where 12 chords build 6 acoustic paths.
Another velocity pattern that frequently occurs, especially downstream of a single elbow or bend in the pipeline, is shown in the picture below. There, just after the bend, the gas mass splits in two contra rotating vortices. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
The average speed of sound is the average of the speed of sound values measured on each of the chords. Normally these values are very close to each other. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Actual volume flow and totalised flow rate values Design Construction The ALTOSONIC V12 measurement system consists of a meter body with ultrasonic transducers and a signal converter for signal processing and counter display on top of the meter body. Nominal diameter DN100...350 / 4"...14": machined out of one piece of metal...
Page 111
Installation conditions Installation Installation For detailed information, refer to on page 18. Dimensions and weights Dimensions and weights For detailed information, refer to on page 115. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 113
Certificate number: EAC RU C-NL..??04.B.00228 Metrology: Metrology: Metrology: Metrology: Pattern certificate number: NL.C.29.004.A No 43620 Custody transfer OIML R137 class 0.5 Certificate NMI CVN-710381-02 Fully compliant with AGA 9 and ISO 17089. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 114
Class I, Zone 1, AEx d e ma IIB, Temperature Class T5, IP Type 4X CANADA (DIV1) Class I, Division 1, Groups C and D Temperature class T5 or T4 Class II/III, DIVISION 1, Group E, F and G, Type 4x; approved process seal www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Qt as per ISO 17089 (Vt = 3 m/s for <12" and Vt=1.5 m/s for ≥ 12" For piping > Sch 80 values can vary slightly. Technical data is provided as indication, please ask KROHNE for detailed sizing. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 121
Qt as per ISO 17089 (Vt = 3 m/s for <12" and Vt=1.5 m/s for ≥ 12" For piping > Sch 80 values can vary slightly. Technical data is provided as indication, please ask KROHNE for detailed sizing. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
10.2 Physical Communication Layer The Modbus over serial line protocol is a master-slave protocol. The physical layer can be half- duplex or full-duplex. In case of the ALTOSONIC V12 the physical layer is a half-duplex (two- wire) connection according to RS 485 specifications.
An advantage of ASCII mode is that it allows for a time interval up to 1 second between characters without causing a timeout. A disadvantage of ASCII mode is the larger message length. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Both character check and message check are generated in the transmitting device and appended to the message before transmission. The slave checks each character and the entire message frame during receipt. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
This interval shall be set long enough for any slave to respond normally. The time out interval is set by a parameter in the master system: request_to_response_timeout request_to_response_timeout request_to_response_timeout request_to_response_timeout. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
– is analyzed and checked one has to be aware of this offset. When functions which do not support broadcast requests, are accessed with a broadcast address, the request will be ignored. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Low) 02(h) 2B(h) 00(h) 00(h) 00(h) 64(h) Table 10-3: Response read holding registers For each register the first byte contains the high order byte, the second the low order byte. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
06(h) 9C(h) 42(h) 00(h) 03(h) Table 10-4: Example write single holding register Response The response message is an echo of the request, returned after the register contents has been written. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
(register 1 is addressed as 0). Example An example of a request for slave device 17 to pre-set two registers starting at 40002 (decimal), 9C42 (hexadecimal) to 00 0A and 01 02 hex: www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
In an exception response the slave sets the most significant bit of the function code to 1. The master recognises the exception response by means of this bit and can examine the data field for the exception code. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Integers are transmitted and stored with the most significant part first. Example Integer value 1790 decimal (6FE hexadecimal) is transmitted as: First transmitted byte in data Second transmitted byte in data field field Table 10-11: Example integer (16 bit) 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
127; also known as exponent bias in the IEEE 754 standard. Example The float number 4.125977 will give the IEEE 754 representation. Example IEEE Sign Exponent Mantissa 1000 0001 (1) 000 0100 0000 1000 0000 0000 www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Double precision bits 2 Mantissa 4 Mantissa 3 Mantissa 2 Mantissa 1 MMMM MMMM MMMM MMMM MMMM MMMM MMMM MMMM Example The double number 4.125000001862645 will give the IEEE representation: 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
The table below shows the maximum number of items per data type: Data type Number of items Boolean 2000 Integer (16 bit) Long integer (32 bit) Float (32 bit floating point) Double (64 bit floating point) Long long (64 bit integer) www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
3000 3000-3001 TestRegister Test Register (2 regs) uint 16 INFORMATION! Register reserved for testing communications and protocol handling with this type of register, without affecting the operation of the flowmeter. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
5000 5000-5001 TestRegister Test Register (2 regs) uint 32 INFORMATION! Register reserved for testing communications and protocol handling with this type of register, without affecting the operation of the flowmeter. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 140
5002-5003 Alarm& S LowFlow Low flow (2 regs) Status Pipe CutOff cut-off Status signal indicating low flow cut-off: 0 = Flow velocity above threshold. 1 = Flow velocity below threshold. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 141
5004 5008-5009 Alarm& A Ch_Deviation_ Channel 3 Down: (2 regs) Status Channel_3 SOS (bit 2) Deviation SoS too large Alarm flag indicating path error (channel 3): SOS deviation too large. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 142
5007 5014-5015 Alarm& A Ch_Deviation_ Channel 6 Down: (2 regs) Status Channel_6 SOS (bit 2) Deviation SoS too large Alarm flag indicating path error (channel 6): SOS deviation too large. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 143
S_RevFail_ Rollover Totaliser (2 regs) Process_Roll FAIL Process (bit 13) Reverse Status signal, totaliser has reached maximum value that can be represented and displayed, totalising is continued starting from zero. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
January 1st, 1970, 00:00:00 hours. Although this is a Holding Register, this register is readonly. Use the KROHNE Flowmeter Configuration and Monitoring software to set or adjust the real- time clock. 10.8.5 Input Registers (read-only): Double (64-bit floating point), address range 6000-...
(12 regs) (= received at trd. A), Channel 1-6 Signal-to-noise ratio for transmission of signal from transducer B towards transducer A, array with values for channel 1 through 6 (in dB). 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 146
37-42 7037-7042 7074-7085 Ch_SoS Channel SOS (6 regs) (12 regs) Channel 1-6 Speed of sound as observed on each channel; array with values for channel 1 through 6 (in m/s). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 147
The series of measurements values then contains the most recent values and shifts with each acquired sample (measurement data), like a running average. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 148
1 through 6. 7078 7156-7157 Weighted_Reliability Overall weighted (2 regs) reliability The reiliabilities of the individual paths are combined in an overall figure using the weighing factors of the paths (in %). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
(short description) 7500 7500-7501 TestRegister Test Register (2 regs) float32 Register reserved for testing communications and protocol handling with this type of register, without affecting the operation of the flowmeter. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 150
For forward flow rates with smaller magnitude than this cutoff value, totalisers stop counting and outputs (such as the frequency output) will be disabled; flow rate indication will still be available (in m/s). www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
Page 151
(2 regs) Proces: LimitHigh Upper limit for process temperature measurement (in ° C). 7525 7550-7551 T_LimitLow Input Temperature (2 regs) Proces: LimitLow Lower limit for process temperature measurement (in ° C). 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
(short description) 8000 8000-8003 TestRegister Test Register (4 regs) uint64 INFORMATION! Register reserved for testing communications and protocol handling with this type of register, without affecting the operation of the flowmeter. www.krohne.com 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en...
(short description) 8500 8500-8503 TestRegister Test Register (4 regs) uint64 INFORMATION! Register reserved for testing communications and protocol handling with this type of register, without affecting the operation of the flowmeter. 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 155
NOTES ALTOSONIC V12 01/2019 - 4002643505 - MA ALTOSONIC V12 R05 en www.krohne.com...
Page 156
• Process Analysis • Services Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.: +49 203 301 0 Fax: +49 203 301 10389 info@krohne.com The current list of all KROHNE contacts and addresses can be found at: www.krohne.com...
Need help?
Do you have a question about the ALTOSONIC V12 and is the answer not in the manual?
Questions and answers