Replacement air temp. aria: this value indicates the outside temperature below
which the heat pump stops and the electric heaters or, if enabled, the boiler, are
used for heating;

9.26 COMPRESSOR HOUR COUNTER MONITOR

This window displays the data relative to the operating hours of the compressors
on the unit:
Hour meter
Circuit 1
Compressor 1:
Compressor 2:
Compressor 3:
Hour meter
Circuit 2
Compressor 1:
Compressor 2:
Compressor 3:

9.27 COMPRESSOR START-UP MONITOR

This window displays the data relative to the compressor start-ups on the unit:
Hour meter
Circuit 1
Number of starts
Compressor 1:
Compressor 2:
Compressor 3:
Hour meter
Circuit 2
Number of starts
Compressor 1:
Compressor 2:
Compressor 3:

9.28 CONFIGURATION OF THE FAN SPEED

This window is used to configure the inverter fan signals:
26
Fans
Fans
Start time:
Minimum V:
Max V cooling:
Max V heating:
0002h
Duration of the initial start: this value indicates the duration of the start at 4V
0002h
when the fans are started;
0002h
Min volt: this value indicates the voltage at minimum speed before shutdown;
Max volt cold: this value indicates the voltage at maximum speed during cooling
mode;
Max volt hot: this value indicates the voltage at maximum speed during heating
mode;

9.29 CONFIGURE MASTER SLAVE

This window is used to configure the parameters for unit Master/Slave manage-
ment:
Installer
0002h
Master/Slave
0002h
0002h
Unit:
Step:
Slave Pump o with
Compressor o :
(Unit: this value indicates the type of setting for the unit; this type can be:
— SINGLE: unit without Master/Slave connection;
— MASTER: identifies the master unit;
— SLAVE: identifies the slave unit;
Power step: the required power calculated by the thermostat is divided between
the master and slave units based on this parameter; (E.G.: 1% = the units work in
parallel; 100%= the units work in sequential mode (first all the power of one is used
0003
and then all the power of the other is used);
Slave pump Off with CP Off: this value indicates management of the pump on the
0002
slave unit; this management can be:
— YES: the slave pump turns off if there is no request on the slave;
0002
— NO: the slave pump turns on and shuts down together with the master;
0003
0002
0002
1s
1.0
10.0
10.0
ALONE
1.0%
NO