Devicenet Wiring; Wiring The Usb Connector - Omron NE1A Series Manual

Safety network controllers
Hide thumbs Also See for NE1A Series:
Table of Contents

Advertisement

Wiring
3-2-4

DeviceNet Wiring

Note
3-2-5

Wiring the USB Connector

Note
Wire the DeviceNet communications cable as shown in the following diagram.
Stickers are placed on the communication connectors based on the color of
each communications wire. By matching the communications wire colors with
the connector sticker colors, you can check to see if wires are in the correct
locations. The colors of the wires are as follows:
Color
Red
V+
White
Signal (CAN H)
-
Drain
Blue
Signal (CAN L)
Black
V−
IMPORTANT
• Turn OFF the power supply to the NE1A-series Controller, to all nodes on
the network, and to communications lines before starting any wiring oper-
ations.
• Tighten the DeviceNet connector to the appropriate torque (0.25 to 0.3
N·m).
• Separate the DeviceNet communications cables from high-voltage/current
lines.
Refer to the DeviceNet Operation Manual (W267) for further information on
wiring.
A computer is connected to use the Network Configurator.
Use a commercially available USB-A to USB-B Male/Male cable to make the
connection.
Use a USB cable of 3 meters max.
Description
Section 3-2
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ne1a-scpu01Ne1a-scpu02

Table of Contents