Command Reference: Function Blocks
Truth Tables
Error Handling and Error Resetting
136
Setting: Single Channel
Input 1
Output
Enable
(NC)
0
0
1
1
0: OFF, 1: ON
Setting: Dual Channel Equivalent
Input 1
Input 2
(NC)
(NC)
0
0
0
1
1
0
1
1
0: OFF, 1: ON
Setting: Dual Channel Complementary
Input 1
Input 2
(NC)
(NO)
0
0
0
1
1
0
1
1
0: OFF, 1: ON
Error
Behavior for error detection
condition
Output
Enable
Discrepancy
OFF
error
(safety
state)
Output
Enable
0
0
0
1
Output
Enable
0
0
1
0
Fault
Error output
Present
ON
Discrepancy
Error output: ON
Section 6-5
Resetting the error
condition
Remove the cause of the error
and then do the following:
1. Make the inputs inactive
and then active again.
2. Or change the NE1A-series
Controller's operating mode
to IDLE Mode and then
back to RUN Mode.