To Use An Rs-485 Connection - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

ESSER Panels
IQ8 Panels

To Use an RS-485 Connection

Using an RS-485 cable, you can connect to the additional RS-485 module (784871) on
the panel's serial interface port.
The RS-485 ports in the gateway board are labeled as 3 and 4 in the
On the Panel Side
Using an SEI2 Card Connect to the RS-485 (784871) module in the panel as below:
In the RXD port of the panel's SEI-2 card:
• Connect the In+ wire to the RXD+ pin.
• Connect the In- wire to the RXD- pin.
Power Connection
Using a power cable, the gateway can connect to the 12V DC power supply module of
the panel.
NOTE: Although the gateway is capable of receiving 24V DC power, it can work with the
12V DC power of the IQ8 panel. Ensure that the power supply to the gateway is within
+12V DC power.
On the Gateway Side
• Connect the +ve wire to the +ve pin of the power supply port.
• Connect the -ve wire to the -ve pin of the power supply port.
On the Panel Side
• Connect the +ve wire to the +UBext pin of the SEI-2 card.
• Connect the -ve wire to the GND pin of the SEI-2 card.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Figure C.7: Wiring Diagram: RS-485 to SEI2 Connection
Connecting to the Panels
Figure
C.2.
113