C.2: Supported Panels; C.3: Am Series Panels; C.3.1: Connection Options; C.3.2: To Use An Rs-232 Connection - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

Supported Panels
C.2 Supported Panels
The CLSS Gateway supports the following panel variants:
AM Series Panels
ESSER Panels
Farenhyt Panels
FireWarden Panels
Gamewell-FCI Panels
Gent Panels
Morley-IAS Panels
NOTIFIER® UL
NOTIFIER® European Panels (EN)
Silent Knight Panels
Triga Panels
VESDA® Detectors
C.3 AM Series Panels
C.3.1 Connection Options
The gateway operates only with the AM Series fire alarm control panels listed in the table
below:
NOTE: The panel can be a stand alone panel or part of a network of panels.
Minimum Required Versions
For the Panel/CPU1: v1.0.703 | For SIB version Panel: v0.68
For the CLSS Gateway: 3.0.4.56
C.3.2 To Use an RS-232 Connection
Using an RS-232 cable the CLSS Gateway and the panel are connected.
The RS-232 port in the gateway board is labeled as 6 in the
1. On the Gateway Side
Connect to an RS-232 port of the gateway board.
2. On the Panel Side
AM8200 Panels
AM8200 Panels
• Connect the White wire to the RX pin of the SIB 8200 board.
• Connect the Green wire to the GND pin of the SIB 8200 board.
• Connect the Brown wire to the TX pin of the SIB 8200 board.
NOTE: Because the SIB 8200 board on the panel connects to the gateway, the SIB board
cannot be used for printing the events.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table C.1: AM Series Panel Connection Options
Fire Alarm Panel Models
AM8200
1
Use the SIB 8200 board
RS-485
UART/TTL
RS-232
No
No
Figure
Connecting to the Panels
USB
1
Yes
No
C.2.
107