C.11: Notifier® European Panels (En); C.11.1: Connection Options; C.11.2: Preparing For Connections; C.11.3: To Use A Nup Connection - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

NOTIFIER® European Panels (EN)
C.11 NOTIFIER® European Panels (EN)
C.11.1 Connection Options
The gateway operates only with the NOTIFIER fire alarm control panels listed in the table
below:
<
NOTE: Compatible CLSS Gateway firmware versions: 3.0.2.30 and above.
C.11.2 Preparing for Connections
For INPIRE panel power connection, you can use either a serial card or an I/O card.
Configure the serial card or the I/O card for the power connection at the Serial
Communication screen of the CLSS Fusion Tool Suite.
Configure the communication settings at the Serial Communication screen of the
CLSS Fusion Tool Suite.
C.11.3 To Use a NUP Connection
Some NOTIFIER panel variants use a NUP connection with the CLSS Gateway.
1. On the Gateway Side
Connect the NUP cable with a pre-formed connector to the NUP port of the gateway
board.
Refer to
Figure C.2
board.
2. On the Panel Side
INSPIRE Panels
• INSPIRE Panels
In the serial communication card on the panel:
• Connect the White wire to the pin 9 (CH2 RX/B).
• Connect the Green wire to the pin 8 (CH2 ISO GND).
• Connect the Brown wire to the pin 10 (CH2 TX/A).
3. Power Connection
The gateway can receive its power either from an external power source or from the
non-resettable internal power of the panel.For the External Power Supply:
NOTE: The external power supply must be dedicated and not shared with any other
devices.
NOTE: The panel's power supply to the gateway must be within +24V DC power.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table C.9: NOTIFIER European Panel Connection Options
Fire Alarm Panel Models
INSPIRE Fusion Panels
E10
E15
1
Use the serial communication card (P/N: HOP-405-100) on the
panel.
2
Use the I/O card (P/N: HOP-404-100) on the panel.
where the NUP port is labeled as 6. It is the P7 pin on the gateway
RS-485
UART/TTL
(RS-232)
No
No
Yes
No
No
Yes
Connecting to the Panels
NUP
USB
1 o r 2
No
3 o r 4
No
141