NOTIFIER® European Panels (EN)
C.11 NOTIFIER® European Panels (EN)
C.11.1 Connection Options
The gateway operates only with the NOTIFIER fire alarm control panels listed in the table
below:
<
NOTE: Compatible CLSS Gateway firmware versions: 3.0.2.30 and above.
C.11.2 Preparing for Connections
For INPIRE panel power connection, you can use either a serial card or an I/O card.
•
Configure the serial card or the I/O card for the power connection at the Serial
Communication screen of the CLSS Fusion Tool Suite.
•
Configure the communication settings at the Serial Communication screen of the
CLSS Fusion Tool Suite.
C.11.3 To Use a NUP Connection
Some NOTIFIER panel variants use a NUP connection with the CLSS Gateway.
1. On the Gateway Side
Connect the NUP cable with a pre-formed connector to the NUP port of the gateway
board.
Refer to
Figure C.2
board.
2. On the Panel Side
•
INSPIRE Panels
• INSPIRE Panels
In the serial communication card on the panel:
• Connect the White wire to the pin 9 (CH2 RX/B).
• Connect the Green wire to the pin 8 (CH2 ISO GND).
• Connect the Brown wire to the pin 10 (CH2 TX/A).
3. Power Connection
The gateway can receive its power either from an external power source or from the
non-resettable internal power of the panel.For the External Power Supply:
NOTE: The external power supply must be dedicated and not shared with any other
devices.
NOTE: The panel's power supply to the gateway must be within +24V DC power.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table C.9: NOTIFIER European Panel Connection Options
Fire Alarm Panel Models
INSPIRE Fusion Panels
E10
E15
1
Use the serial communication card (P/N: HOP-405-100) on the
panel.
2
Use the I/O card (P/N: HOP-404-100) on the panel.
where the NUP port is labeled as 6. It is the P7 pin on the gateway
RS-485
UART/TTL
(RS-232)
No
No
Yes
No
No
Yes
Connecting to the Panels
NUP
USB
1 o r 2
No
3 o r 4
No