ESSER Panels
C.4 ESSER Panels
The gateway should have an RS-485 connection with the panel for sending events. If
Inventory Synchronization is required, use the RS-232 connection.
C.4.1 Connection Options
The gateway operates only with the ESSER fire alarm control panels as listed in the table
below:
Minimum Required Versions
FlexES panel: 4.07R001
IQ8 panel: 03.13R000
CLSS Gateway: 3.1.4.72
C.4.2 To Use an RS-485 Connection
Using an RS-485 cable the CLSS Gateway and the panel are connected.
The RS-485 ports in the gateway board are labeled as 3 and 4 in the
1. On the Gateway Side
Connect to an RS-485 port of the gateway board.
2. On the Panel Side
FlexES Panels
IQ8 Panels
FlexES Panels
• Connect the +ve wire to the Terminal 1 of the panel.
• Connect the -ve wire to the Terminal 2 of the panel.
Figure C.4: Wiring Diagram: RS-485 Connections for a FlexES Panel
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table C.2: ESSER Panel Connection Options
Fire Alarm Panel Models
FlexES Control
IQ8Control C
IQ8Control M
1
Use a TTY-RS-232 converter (764856)
2
Use the RS-485 module (784871)
3
Use the add-on SEI-2 (Serial Essernet® Interface) (784850)
RS-485
UART/TTL
Yes
No
2
3
and
Yes
No
2 and 3
Yes
No
Connecting to the Panels
RS-232
USB
1
Yes
No
1
Yes
No
1
Yes
No
Figure
C.2.
109