2 - SAFETY CONSIDERATIONS

WARNING: Switch off the main electrical power
supply to the unit and accessories (if installed)
before doing any work on the unit.

2.1 - General

Installing, commissioning and servicing of the various
component  (unit,  control  system,  hot  and  cold  water 
system,  air  distribution  system)  can  be  dangerous 
unless certain aspects of the installation, such as the
presence of mains electricity and hot or cold water in 
the air conditioning equipment, are taken into account.
Only  specially  trained  and  qualified  technicians  and 
installers  who  have  been  fully  trained  on  the  product 
concerned are authorised to install, commission and
service this equipment.
During  servicing  work,  it  is  essential  to  apply  all 
recommendations and instructions given in service
leaflets, on labels or in the instructions delivered with 
the equipment, and to comply with any other relevant 
instructions.
Definition of the pictograms used:
■ Electrical danger
■ Caution hand hazard
■ General danger
Comply with all safety rules and regulations currently in 
force. Wear eye protectors and work with hand gloves 
and any individual protection equipment following local 
legislation. Take care when moving or positioning of the 
equipment.

2.2 - Protection against electrocution

Only personnel qualified to perform electrical and
maintenance work may make electrical connections. In 
particular it is obligatory to disconnect all power supplies 
to the unit and its accessories before carrying out any
work.  Disconnect  the  main  power  supply  with  an 
isolating device (not supplied by Carrier).
IMPORTANT: The components, which make up the
different control loops described in this manual
include electronic items. As such, they may
generate or be harmed by electromagnetic
interference unless they are installed and used in
accordance with these instructions. The components
making up these control systems conform to the
requirements of electromagnetic compatibility in
residential, commercial and light industrial areas.
They also comply with the low-voltage directive.
If the product is supplied without a Carrier control device, 
verification  of  EMC  conformity  is  the  responsibility  of 
the installer.
- Fig.4
- Fig.5
- Fig.6

2.3 - General installation conditions

IMPORTANT: The Carrier numeric controller, power
module, or in general units fitted with controls loops
must have an isolating device upstream (for
example a double-pole circuit breaker). If necessary,
an easily operated emergency stop device (such as
a punch-button switch) must cut off the power to
all equipment. The installation must be equipped
with a device to protect against earth faults. The
disconnect device must simultaneously disconnect
the two poles (phase and neutral), and have a
distance of at least 3 mm between the contacts, in
compliance with the installation instructions. The
mains power cable must have 3 conductors (blue,
brown, green/yellow) and its cross section and type
must comply with the specifications set out by the
applicable EN or IEC standard. Refer to the selection
sheet or the name plate to determine the maximum
input current. These devices are not supplied by
Carrier.
In general terms the following rules must be applied:
Upstream over voltage protection
Size (42NL & 42NH)
2_5; 2_9
3_5; 3_9
4_5; 4_9
5_5; 5_9
6_5; 6_9
7_9; 7_9
Size (42NL & 42NH)
[0-1400W]
2_5; 2_9
3_5; 3_9
4_9
4_5
5_5; 5_9
6_5; 6_9
7_5; 7_9
■ Electrical connections must be made according to
the  wiring  diagram  provided  with  the  unit  and  the 
installation and operation manual of the controller.
■ Units must be provided with over-voltage protection 
upstream (not supplied by Carrier).
■ The  power  disconnection  device  must  be  clearly 
labelled  to  identify  which  items  of  equipment  are 
connected to it.
■ The  wiring  of  the  components  which  make  up  the 
different control systems and the communication
buses  must  be  carried  out  in  accordance  with  the 
latest rules and regulations by professional installers.
Without Elec. Heater
T2A
T2A
T2A
T3A
T3A
T3A
With Elec. Heater
[1500-
[3000-
2400W]
3200W]
T10A
NA
NA
T10A
NA
NA
T10A
NA
NA
T10A
T16A
NA
T10A
T16A
NA
T10A
T16A
T20A
T10A
T16A
T20A
13