Optional Electric Heater; Optional Water Sensor; Optional Condensate Pump - Carrier Idrofan 42NL Installation, Operating And Maintenance Instruction

Ducted fan coil units
Table of Contents

Advertisement

4 - COMPONENTS AND MAINTENANCE

4.10 - Optional electric heater

WARNING: Disconnect the power supply before
carrying out any work on the unit.
If the electric heater develops a fault, it must be
replaced; this requires the removal of the fan motor
assembly: Fig. 12.
CAUTION: Do not touch the live metal heater
elements when the electric heater is connected to
the power supply.
Electric heater replacement procedure:
■ Remove the filter.
■ Remove the fan motor assembly access panel.
■ Identify and note the fan speeds wired to the auto-
transformer  terminal  block.  Disconnect  the  power 
supply cable.
■ Remove the fan motor assembly.
NOTE: Be careful not to touch the fan blades during
the removal process to avoid unbalancing the fans.
■ Disconnect the electric heater power supply cables 
and remove them through the cable conduit.
■ Unscrew the defective heater(s) and replace it (them).
■ Replacement of the fan motor assembly is by the
reversal of the above procedure.Carrier Electronic
thermostat type B is embedded with Electric heater 
relay 8 Amps. Accordingly, Carrier requires an
additional  protection  relay  for  electric  heater  with 
above 1400 W capacity.
All  units  delivered  with  an  electrical  box  or  a  Carrier 
controller  are  always  equipped  with  a  relay  if  the 
capacity of the electrical heater is above 1400W.
WARNING : In case of customer supplied controller,
it is the responsability of the installer to set up an
additional protection relay corresponding to the
electrical heater capacity.
22

4.11 - Optional water sensor

A water temperature sensor can be provided. It has to 
be installed on the water circuit as described below :
■ For  2-pipe  coil  :  the  sensor  shall  be  installed  on  a 
cooling  water  pipe  (for  change-over  function). The 
sensor is installed on a part where the water flow is 
continuous.
■ For  4-pipe  coil  :  the  sensor  shall  be  installed  on  a 
heating  water  pipe  (for  cold-draft  function  that 
prevents the operation of the unit when the heating 
network is off).
NOTE: In case of unit with an electrical box (for
Carrier Thermostats), a "switch" is provided as an
option instead of the water sensor.

4.12 - Optional condensate pump

Check the sealing of the hydraulic connection of the
condensate pump and condensate recovery.
The meaning of the electrical wires is described below:
■ Brown - Blue wires : Electrical supply 230V 50/60Hz
■ Black - Grey wires : Alarm contact Normally Closed 
(NC) 250V/8A maxi.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Idrofan 42nh

Table of Contents