4 - COMPONENTS AND MAINTENANCE

4.6 - Optional filter and filter access

4.6.1 - Description
The Carrier unit is fitted with G1 filter as standard.
A G3 or M5 filter is also available as an option
G3 and M5 filters both comply with the M1 fire class.
Different filter access are available:
■ Unit without rectangular flange air inlet (plain inlet): 
access is from the rear of the unit.
■ Unit with rectangular flange air inlet or with return air 
plenum: access is from below (trapdoor).
4.6.2 - Air filter replacement
Air filters should be changed regularly. Filter life depends 
on the rate at which the filter becomes clogged, which 
depends  upon  the  cleanliness  of  the  working 
environment.
If clogged filters are not changed they can increase the 
air pressure drop, trapped dust particles may be given
off and entrained in the air supply, and the general
performance  of  the  unit  may  be  degraded  (as  the  air 
flow reduces).
NOTE: When installing a unit in a ceiling void, check
that no T-bars will obstruct filter access and
removal.

4.7 - Fresh air controller

4.7.1 - Fresh air controller with (adjustable)
constant air volume
The unit can be fitted with three ranges of constant and 
adjustable fresh air flow. The 3 ranges are 15 to 50 m
50 to 100 m
/h and 100 to 180 m
3
The  diameter  of  the  spigot  housing  the  fresh  air  flow 
controller is 125 mm. The fresh air controller can be
modified  on  site  by  unscrewing  and  repositioning  the 
damper of the controller. See fig 17.
IMPORTANT: If the unit is fitted with a return air
temperature sensor, the constant fresh air flow rate
must not exceed 50% of the supply air flow delivered
by the unit at minimum speed.
NOTE: To operate correctly the constant fresh air
flow controller requires a differential pressure in the
range of 60 Pa to 210 Pa.
/h,
3
/h.
3
4.7.2 - Fresh air controller with variable air
volume
The unit can be equipped with a variable fresh air flow 
controller from 0 to 55 l/s (0 to 200 m
This is connected to the numeric Carrier controller and
can regulate the fresh air intake in two ways:
■ Either using a fixed rate set by the installer that can 
be reconfigured as required
■ Or based on the CO
2
to a CO
sensor via the Carrier numeric controller
2
(the  CO
sensor is located opposite the fresh air
2
inlet).
NOTE: With the variable fresh air flow controller the
upstream pressure in the fresh air duct must be 180
Pa. It is available as an accessory.
4.7.3 - Fresh air filtration
If the unit is provided without any filter or if the fresh air 
inlet is fitted in the base unit or in the return plenum, it 
is the responsibility of the installer to check if the fresh
air is filtered beforehand.
4.8 - Optional water flow control
valves
These valves are either two-way or four-way type (three-
way  with  integral  bypass).  The  body  of  the  valve  is 
designed  to  withstand  a  15.5  bar  (1550  kPa)  bar 
operating pressure.
With this option, the couple (valve + actuator) is usually 
normally closed (NC).Thus, the water flow is null in case 
of power cut. To fill the installation, to equalise the water 
circuits and to purge the units, the actuators must be
connected to the power supply and the valves must be 
opened via the controller (thermostats or BMS).
For the replacement of these components refer to the
chapter 4.8.4. - ''Actuator replacement procedure''.